5.1.7
Settings
5.1.7.1
TCSSCBR Non group settings
Table 172: TCSSCBR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
5=off
Operation Off / On
Operate delay time 20...300000
ms
1
3000
Operate delay time
Table 173: TCSSCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
20...60000
ms
1
1000
Reset delay time
5.1.8
Monitored data
5.1.8.1
TCSSCBR Monitored data
Table 174: TCSSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
TCSSCBR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.1.9
Technical revision history
Table 175: TCSSBR Technical revision history
Technical revision
Change
B
Internal improvement
C
Internal improvement
5.2
Current circuit supervision CCSPVC
Supervision functions
1MRS758407 C