Table 658:
SECRSYN Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Synchro check mode
1=Off
2=Synchronous
3=Asynchronous
3=Asynchronous
Synchro check operation mode
Dead line value
0.1...0.8
xUn
0.1
0.2
Voltage low limit line for energizing check
Live line value
0.2...1.0
xUn
0.1
0.8
Voltage high limit line for energizing check
Dead bus value
0.1...0.8
xUn
0.1
0.2
Voltage low limit bus for energizing check
Live bus value
0.2...1.0
xUn
0.1
0.5
Voltage high limit bus for energizing check
Max energizing V
0.50...1.15
xUn
0.01
1.05
Maximum voltage for energizing
Table 659:
SECRSYN Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Control mode
1=Continuous
2=Command
1=Continuous
Selection of synchro check command or
Continuous control mode
Close pulse
200...60000
ms
10
200
Breaker closing pulse duration
Phase shift
-180...180
deg
1
0
Correction of phase difference between
measured U_BUS and U_LINE
Minimum Syn time
0...60000
ms
10
0
Minimum time to accept synchronizing
Maximum Syn time
100...6000000
ms
10
2000
Maximum time to accept synchronizing
Energizing time
100...60000
ms
10
100
Time delay for energizing check
Closing time of CB
40...250
ms
10
60
Closing time of the breaker
Voltage source switch
0=False
1=True
0=False
Voltage source switch
9.3.8
Monitored data
Table 660:
SECRSYN Monitored data
Name
Type
Values (Range)
Unit
Description
ENERG_STATE
Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
Energization state of Line
and Bus
U_DIFF_MEAS
FLOAT32
0.00...1.00
xUn
Calculated voltage
amplitude difference
FR_DIFF_MEAS
FLOAT32
0.000...0.100
xFn
Calculated voltage
frequency difference
PH_DIFF_MEAS
FLOAT32
0.00...180.00
deg
Calculated voltage phase
angle difference
U_DIFF_SYNC
BOOLEAN
0=False
1=True
Voltage difference out of
limit for synchronizing
Table continues on next page
1MRS758755 A
Section 9
Control functions
REC615 and RER615
629
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...