![ABB RELION Series Technical Manual Download Page 574](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191574.webp)
Name
Type
Values (Range)
Unit
Description
U_INST_CA
FLOAT32
0.00...4.00
xUn
U31 Amplitude,
magnitude of
instantaneous value
U_ANGL_CA
FLOAT32
-180.00...180.00
deg
U31 angle
U_DB_CA
FLOAT32
0.00...4.00
xUn
U31 Amplitude,
magnitude of reported
value
U_DMD_CA
FLOAT32
0.00...4.00
xUn
Demand value of U31
voltage
U_RANGE_CA
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
U31 Amplitude range
U_INST_A
FLOAT32
0.00...5.00
xUn
UL1 Amplitude,
magnitude of
instantaneous value
U_ANGL_A
FLOAT32
-180.00...180.00
deg
UL1 angle
U_DMD_A
FLOAT32
0.00...5.00
xUn
Demand value of UL1
voltage
U_INST_B
FLOAT32
0.00...5.00
xUn
UL2 Amplitude,
magnitude of
instantaneous value
U_ANGL_B
FLOAT32
-180.00...180.00
deg
UL2 angle
U_DMD_B
FLOAT32
0.00...5.00
xUn
Demand value of UL2
voltage
U_INST_C
FLOAT32
0.00...5.00
xUn
UL3 Amplitude,
magnitude of
instantaneous value
U_ANGL_C
FLOAT32
-180.00...180.00
deg
UL3 angle
U_DMD_C
FLOAT32
0.00...5.00
xUn
Demand value of UL3
voltage
8.1.5.6
Technical data
Table 579:
VMMXU Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage
measured: f
n
±2 Hz
At voltages in range 0.01…1.15 × U
n
±0.5% or ±0.002 × U
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
Section 8
1MRS758755 A
Measurement functions
568
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...