8.1.5.3
Signals
Table 574:
VMMXU Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase to earth voltage A or phase to phase voltage
AB
U_B_BC
SIGNAL
0
Phase to earth voltage B or phase to phase voltage
BC
U_C_CA
SIGNAL
0
Phase to earth voltage C or phase to phase voltage
CA
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 575:
VMMXU Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
LOW_WARN
BOOLEAN
Low warning
LOW_ALARM
BOOLEAN
Low alarm
8.1.5.4
Settings
Table 576:
VMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit
supervision
V high high limit
0.00...4.00
xUn
1
1.40
High alarm voltage limit
V high limit
0.00...4.00
xUn
1
1.20
High warning voltage limit
V low limit
0.00...4.00
xUn
1
0.00
Low warning voltage limit
V low low limit
0.00...4.00
xUn
1
0.00
Low alarm voltage limit
V deadband
100...100000
1
10000
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 577:
VMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
Section 8
1MRS758755 A
Measurement functions
566
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...