![ABB RELION Series Technical Manual Download Page 559](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191559.webp)
Section 8
Measurement functions
8.1
Basic measurements
8.1.1
Functions
The three-phase current measurement function CMMXU is used for monitoring and
metering the phase currents of the power system.
The three-phase voltage measurement function VMMXU is used for monitoring and
metering the phase-to-phase voltages of the power system. The phase-to-earth
voltages are also available in VMMXU.
The residual current measurement function RESCMMXU is used for monitoring and
metering the residual current of the power system.
The sequence current measurement CSMSQI is used for monitoring and metering the
phase sequence currents.
The sequence voltage measurement VSMSQI is used for monitoring and metering the
phase sequence voltages.
The frequency measurement FMMXU is used for monitoring and metering the power
system frequency.
The three-phase power and energy measurement PEMMXU is used for monitoring
and metering active power (P), reactive power (Q), apparent power (S) and power
factor (PF) and for calculating the accumulated energy separately as forward active,
reversed active, forward reactive and reversed reactive. PEMMXU calculates these
quantities using the fundamental frequency phasors, that is, the DFT values of the
measured phase current and phase voltage signals.
The information of the measured quantity is available for the operator both locally in
LHMI or WHMI and remotely to a network control center with communication.
If the measured data in LHMI or WHMI is within parentheses, there
are some problems to express the data.
8.1.2
Measurement functionality
The functions can be enabled or disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
553
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...