5.3.7
Settings
Table 509:
TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Trip pulse time
20...60000
ms
1
250
Minimum duration of trip output signal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched
Select the operation mode for trip output
5.3.8
Monitored data
Table 510:
TRPPTRC Monitored data
Name
Type
Values (Range)
Unit
Description
TRPPTRC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.3.9
Technical revision history
Table 511:
TRPPTRC Technical revision history
Technical revision
Change
B
-
C
-
D
Internal improvement.
E
Setting
Trip output mode default setting is
changed to "Latched".
F
Internal improvement.
5.4
Fault locator SCEFRFLO
5.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator
SCEFRFLO
FLOC
21FL
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
481
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...