4.2.7.9
Technical data
Table 392:
MFADPSDE Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)
Typically 35 ms
Reset time
Typically 40 ms
Operate time accuracy
±1.0% of the set value or ±20 ms
1) Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
4.3
Unbalance protection
4.3.1
Negative-sequence overcurrent protection NSPTOC
4.3.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overcurrent
protection
NSPTOC
I2>
46
4.3.1.2
Function block
A070758 V1 EN
Figure 205:
Function block
4.3.1.3
Functionality
The negative-sequence overcurrent protection function NSPTOC is used for
increasing sensitivity to detect single-phase and phase-to-phase faults or unbalanced
loads due to, for example, broken conductors or unsymmetrical feeder voltages.
NSPTOC can also be used for detecting broken conductors.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
395
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...