Section 4
Protection functions
4.1
Three-phase current protection
4.1.1
Three-phase non-directional overcurrent protection
(F)PHxPTOC
4.1.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase non-directional
overcurrent protection, low stage
(F)PHLPTOC
3I>
51P-1
Three-phase non-directional
overcurrent protection, high stage
PHHPTOC
3I>>
51P-2
Three-phase non-directional
overcurrent protection, instantaneous
stage
PHIPTOC
3I>>>
50P/51P
4.1.1.2
Function block
PHHPTOC
I_A
I_B
START
OPERATE
I_C
BLOCK
ENA_MULT
FPHLPTOC
I_A
I_B
START
OPERATE
I_C
BLOCK
ENA_MULT
PHIPTOC
I_A
I_B
START
OPERATE
I_C
BLOCK
ENA_MULT
GUID-42271A6F-6299-4B1A-B55D-AC1A516BC662 V1 EN
Figure 113:
Function block
4.1.1.3
Functionality
The three-phase non-directional overcurrent protection function (F)PHxPTOC is
used as one-phase, two-phase or three-phase non-directional overcurrent and short-
circuit protection.
The function starts when the current exceeds the set limit. The operate time
characteristics for low stage (F)PHLPTOC and high stage PHHPTOC can be selected
to be either definite time (DT) or inverse definite minimum time (IDMT). The
instantaneous stage PHIPTOC always operates with the DT characteristic.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
201
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...