Signals
Table 121:
RS Input signals
Name
Type
Default
Description
S
BOOLEAN
0=False
Set Q output when set
R
BOOLEAN
0=False
Resets Q output when
set
Table 122:
RS Output signals
Name
Type
Description
Q
BOOLEAN
Q status
NOTQ
BOOLEAN
NOTQ status
Technical revision history
Table 123:
RS Technical revision history
Technical revision
Change
L
The name of the function has been changed from
SR to RS.
3.16.2
Minimum pulse timer
3.16.2.1
Minimum pulse timer TPGAPC
Function block
GUID-809F4B4A-E684-43AC-9C34-574A93FE0EBC V1 EN
Figure 78:
Function block
Functionality
The Minimum pulse timer function TPGAPC contains two independent timers. The
function has a settable pulse length (in milliseconds). The timers are used for setting
the minimum pulse length for example, the signal outputs. Once the input is activated,
the output is set for a specific duration using the
Pulse time
setting. Both timers use the
same setting parameter.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
133
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...