ABB RELION Series Communication Protocol Manual Download Page 29

The Analog Output Block DNP3 object group (41) is used for writing to a DNP3
analog output. Analog output can be also read from the protection relay, as object
group 40. Reading an analog output returns the last written value to the object.

Class events are generated for changed Analog Output values. The DNP3 Analog
Output event buffer size is 100.

3.6 

Fault records

Fault record data objects contain registered values captured simultaneously by the
relay's protection at the moment of a fault. The fault record objects internally belong to
IEC 61850 logical node FLTRFRC1.

The FLTRFRC1 objects can be found as DNP3 analog input values in the DNP3 point
list. There are two alternative DNP3 data objects for each captured fault record object
in the point list. A different trailing text for the objects is shown in the object's name,
either “Ev-Upd” (event updated) or “Record” (read on demand).

3.6.1 

Ev-Upd type objects

A freely selectable part of the “Ev-Upd” objects, or alternatively all objects can be
added to the DNP3 analog input data memory map. These objects can also be enabled
for DNP3 class events. Each time a new fault record capture is done by the protection
relay, the objects are sent as DNP3 class events to the controlling station. Every object
captured at the same time (belonging to the same record) has the same time tag. The
controlling station can also, at any time, read fault record objects from the outstation.
The most recent (newest) captured value is always returned.

The deadband setting for the “Ev-Upd” objects should be “0”. This means that every
update of the object from the protection relay level is propagated as a DNP3 class
event, regardless of the change in value. As a default setting, all analog inputs have
deadband setting of 0.0, that is, the event is always reported when a system event is
generated. In the fault record, the next captured value can be identical to the previous
one, therefore the recommended deadband value is 0.0.

3.6.2 

Record type objects

The protection relay saves the 128 latest captured fault records internally. On demand,
these (older) records can be read by the DNP3 controlling station.

A freely selectable part of the “Record” objects can be added to the DNP3 analog input
data memory map. These objects are as default defined as ‘Static only’. This means
that they can only be read on demand by the controlling station. Also notice the analog
output object from the same logical node named FLTRFRC1.SelRow.ctlVal ‘-Select
record’. This object should be added to the DNP3 analog output area.

1MRS758757 A

Section 3

Vendor-specific implementation

REC615 and RER615

23

Communication Protocol Manual

Summary of Contents for RELION Series

Page 1: ...RELION PRODUCT FAMILY Grid Automation REC615 and RER615 DNP3 Communication Protocol Manual...

Page 2: ......

Page 3: ...Document ID 1MRS758757 Issued 2018 08 31 Revision A Product version 2 0 Copyright 2018 ABB All rights reserved...

Page 4: ...this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group Al...

Page 5: ...ted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administrat...

Page 6: ...concerning electrical equipment for use within specified voltage limits Low voltage directive 2014 35 EU This conformity is the result of tests conducted by ABB in accordance with the product standar...

Page 7: ...nections 10 Protocol data mapping to server instances 11 Link modes 11 Serial link mode 11 TCP IP mode 12 Communication setup 12 Communication modes 12 DNP3 layer acknowledgements retries and timeouts...

Page 8: ...physical outputs 22 Control feedback 22 Analog outputs 22 Fault records 23 Ev Upd type objects 23 Record type objects 23 Time stamp for record type objects 24 Additional fault record implementation d...

Page 9: ...e communication system engineer or system integrator responsible for pre engineering and engineering the communication setup in a substation from a protection relay s perspective The system engineer o...

Page 10: ...ual IEC 61850 Engineering guide Point list manual GUID 7414985D 2433 46E4 B77B CCE64F6FC8D0 V2 EN Figure 1 The intended use of documents during the product life cycle Product series and product specif...

Page 11: ...to the concept discussed in the text It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property The information icon alerts the reader o...

Page 12: ...the changes in nonvolatile memory select Yes and press Parameter names are shown in italics The function can be enabled and disabled with the Operation setting Parameter values are indicated with quo...

Page 13: ...ed protocol stack is referred to as EPA However to support advanced RTU functions and messages larger than the maximum frame length as defined by the IEC document 60870 5 1 the DNP3 data link is inten...

Page 14: ...8...

Page 15: ...ll the clients should be able to access exactly similar data or similar data outlook The default protocol mapping or data outlook can be modified freely 3 Several clients Several protocol instances Se...

Page 16: ...ting parameters in an instance Client IP When the client makes the TCP connection its IP address is checked This instance is given to the client with this IP address It is also possible to use the add...

Page 17: ...r 3 2 1 Serial link mode DNP3 serial can be assigned to a serial communication port in the protection relay Serial communication ports are named COM1 COMn depending on how many serial ports the protec...

Page 18: ...y exception In this mode the DNP3 client always initiates the transaction with a read or write request to the DNP3 server The server must reply with a response message Unsolicited mode called also Uns...

Page 19: ...Unsolicited reporting mode Unsolicited mode can be enabled in the relay by the UR mode parameter The operating principle is that the server sends event data spontaneously to the client When the unsol...

Page 20: ...ch can be used in both Ethernet TCP IP and serial communication modes When the client has successfully established connection to the protection relay keep alive messages are sent periodically by the c...

Page 21: ...rotocol mapping errors noticed Status Shows the value True if the TCP IP or serial instance is active This means that a DNP3 client has connected to the TCP socket and DNP3 messages are received regul...

Page 22: ...figuration It is impossible to make the DNP3 point configuration before the protection relay s application configuration has been created If a function block is removed from the configuration the DNP3...

Page 23: ...bjects The control command issued to the control object is only a trigger In a protection relay the control object knows how to perform the physical control operation In CROB data the given pulse type...

Page 24: ...ation Remote Off or All state A DNP3 controlling station can perform control operations in Station Remote and All protection relay states However it is the controlled protection relay s application in...

Page 25: ...t can be connected to a general purpose input and accessed by the legacy protocol as regular protocol application data General purpose input object and OR function block may cause delays to time stamp...

Page 26: ...ting for the default variation of DNP3 analog data is float32 If needed the default variation can be changed to integer 16 or 32 bit types In such case re scaling of the original data has to be applie...

Page 27: ...wo types of counters in the relay BCR class is an integrated totals type counter typically used for energy values INC class counters are operational counters for example circuit breaker control counte...

Page 28: ...oint control the IEC 61850 standard defines a value attribute named stSeld to be always available for the control object In case of SBO this value shows if the control object is actually selected for...

Page 29: ...he controlling station Every object captured at the same time belonging to the same record has the same time tag The controlling station can also at any time read fault record objects from the outstat...

Page 30: ...eral alternatives for any remote client including DNP3 to access the captured fault record data Alternative 1 buffering on the DNP3 client side The easiest alternative is that the client receives the...

Page 31: ...ion blocks that have been added into the protection relay s configuration using Application Configuration in PCM600 The IED system data is always available and is not dependent on the application conf...

Page 32: ...26...

Page 33: ...munication interface selection Unit address 1 65519 1 1 DNP unit address Master address 1 65519 1 3 DNP master and UR address Mapping select 1 2 1 1 Mapping select ClientIP 0 0 0 0 IP address of clien...

Page 34: ...UR offline interval 0 65535 min 1 15 Unsolicited offline interval UR Class 1 Min events 0 999 1 2 Min number of class 1 events to generate UR UR Class 1 TO 0 65535 ms 1 50 Max holding time for class...

Page 35: ...it Cnt evt 2 2 16bit Cnt evt 5 5 32bit Cnt evt time 6 6 16bit Cnt evt time 6 6 16bit Cnt evt time 1 32 bit counter event 2 16 bit counter event 5 32 bit counter event with time 6 16 bit counter event...

Page 36: ...8 8 double AO evt time 4 4 16bit AO evt time 1 32 bit AO event 2 16 bit AO event 3 32 bit AO event with time 4 16 bit AO event with time 5 float AO event 6 double AO event 7 float AO event with time 8...

Page 37: ...nal Electrotechnical Commission IEC 60870 5 IEC standard for telecontrol equipment and systems Part 5 defines transmission protocols IEC 61850 International standard for substation communication and m...

Page 38: ...nt status TCP Transmission Control Protocol TCP IP Transmission Control Protocol Internet Protocol WHMI Web human machine interface Section 5 1MRS758757 A Glossary 32 REC615 and RER615 Communication P...

Page 39: ...33...

Page 40: ...ribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 www abb com mediumvoltage www abb com substationautomation Copyright 2018 ABB All rights reserved 1MRS7...

Reviews: