The operational mode as given by the Mode control is shown in the data object Beh according to
priority rules described for Beh in clause 6 of IEC 61850-7-4.
The Beh shows the actual state of the function depending on the hierarchy described in clause 6 of
IEC 61850-7-4.
It is possible that the behavior is influenced also by other sources independent from the Mod, for
example Insertion of the test handle, IED configuration tool (PCM600), or LHMI.
In case the setting
operation
of a function is set to
Off
from the LHMI or PCM600, the Beh will be set
to
Off
independent of the value of the Mod.
The state
Off
can be set from the LHMI or the PCM600 for the functions having the setting
operation
.
The TEST and the TEST/BLOCKED mode can be operated locally from the LHMI or by using
PCM600.
Health
Health will reflect the current status of the IED HW and configuration. Possible values are: OK,
Warning, and Alarm.
Health indicates OK, Warning, or Alarm, depending on the IED status.
NamePlt
The name of the logical node and its relation to namespace definition are shown in the data object
NamePlt as specified for the SCL structure.
7.2
IEC 61850 data model description Edition 2
GUID-B7C6120F-3A98-4DD4-8B4B-CCD2EEC9EE29 v3
The IEC 61850 data model description Edition 2 is delivered in online help format on the IED
Connectivity package USB flash drive as part of the product delivery. The latest versions can be
downloaded from
www.abb.com/protection-control
.
7.2.1
Using the online help file
GUID-0436EB93-842F-4908-85CB-93BCFED7AC93 v8
1.
Download the online help file from the link below and save the file to your local hard drive.
•
) for IEC 61850 data model description, Edition 2, SAM600–IO 2.2
2.
Double-click the file.
3.
Clear the
Always ask before opening this file
check box.
4.
Click
Open
.
7.2.2
DO presence condition description
GUID-63E36A26-DCFF-49CD-9C58-CE783031532C v2
Table 3:
Conditions used by the Logical Node description
Condition
Description
AtLeastOne
At least one of marked elements shall be present.
M
Element is mandatory.
MFcond
Not yet defined.
Mmulti
At least one element shall be present; all instances have an instance number within range [1,
99] (see Part 7-1).
Table continues on next page
Section 7
1MRK 511 441-UEN Rev. C
Logical node data model
32
Switchgear control unit SAM600-IO
Communication protocol manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved