DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
AccAPwr
v2_dMV
q
MX
-
IPOWPH
Mon
Quality: Accumulated
I^CurrExponent integrated over
CB open travel time
t
MX
-
IPOWPH
Mon
Timestamp: Accumulated
I^CurrExponent integrated over
CB open travel time
PresAlm
v3_dSPS
stVal
ST
-
GPRESALM
Mon
Pressure below alarm level
q
ST
-
GPRESALM
Mon
Quality: Pressure below alarm
level
t
ST
-
GPRESALM
Mon
Timestamp: Pressure below
alarm level
OpCnt
v5_dINS
stVal
ST
-
NOOPER
Mon
Number of CB operation cycle
q
ST
-
NOOPER
Mon
Quality: Number of CB operation
cycle
t
ST
-
NOOPER
Mon
Timestamp: Number of CB
operation cycle
GUID-B3D47A00-E233-4E54-910F-97BCD32C501A v1
Since there is no current measurement functionality in SAM600-IO,
evaluation of the following parameters are not possible in the
circuit breaker condition monitoring function (SSCBR):
•
Circuit breaker status
•
Remaining life of the circuit breaker
•
Contact erosion estimation
•
Circuit breaker contact travel time
Setting parameters
AccmPwrAlm
,
AccmPwrLo
,
CBLifeAlm
,
RmnNumOp
,
ClsAlm
,
OpnAlm
,
AccmAPwr
,
RsAccmAPwr
,
RsRmnNumOp
, and
RsTrvTm
are not available in SAM600-IO.
7.8.2
Insulation medium supervision (gas) SIMG
7.8.2.1
Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
PID-3703-LOGICALNODEDATA v3
LN type
LN prefix LN class Function block name
SSIMG (revision 0) S
SIMG
SSIMG
1MRK 511 440-UEN A
Section 7
Logical node data model
Switchgear control unit SAM600-IO Version 2.2 IEC
73
Communication protocol manual