Section 3 

Substation Configuration description

Language (SCL)

SEMOD129808-4 v8

Four different types of SCL files - SCD, CID, IID, and ICD, can be exported from
PCM 600.

The SCL language is based on XML. However, detailed knowledge of the XML
contents is not needed.

The SCL XML file (ICD/SCD/CID/IID) contains five sections, which are specified
in IEC 61850–6 clause 9.

Header

Substation section describes the functional structure and its relation to primary
devices.

Communication section describes the connection between the IED access
points to the respective subnetwork. and includes also the properties
(addresses) of the access points.

IED section contains a description of the supported communication services,
the access point(s) and the IEDs logical devices, logical nodes and their
attributes.

Data type template section contains a declaration of all types used in the SCL
file, logical nodes type, DO types, attributes and enums.

The system structure is defined by the organization of the plant structure in
PCM600. The signal engineering and the signal routing are IET600 tasks, signal
engineering regarding DS, rcb,gcb, GOOSE subscribers can be done also in
PCM600. The IED needs to be configured with PCM600 before the system is
configured with IET600.

The SCL engineering must be done in an SCL engineering tool. The data sets and
the control blocks are logically defined as part of the logical nodes (see IEC
61850–7–2 clause 9). The IED also needs a correctly configured communication
section for GOOSE engineering, which can be done in IET600 or PCM600.

The data type templates section provides the correct content description of each
logical node type to all tools and users (clients) of the information. Each IED and
vendor may have their own logical node type definitions included in the data type
template section together with all other logical node types based on the standard.

1MRK 511 440-UEN A

Section 3

Substation Configuration description Language (SCL)

Switchgear control unit SAM600-IO Version 2.2 IEC

15

Communication protocol manual

Summary of Contents for Relion SAM600-IO

Page 1: ... RELION SAM600 Switchgear control unit SAM600 IO Version 2 2 IEC IEC 61850 Edition 1 communication protocol manual ...

Page 2: ......

Page 3: ...Document ID 1MRK 511 440 UEN Issued November 2017 Revision A Product version 2 2 Copyright 2017 ABB All rights reserved ...

Page 4: ...erms of such license This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit http www openssl org This product includes cryptographic software written developed by Eric Young eay cryptsoft com and Tim Hudson tjh cryptsoft com Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be...

Page 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Page 6: ...nd concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standards of ...

Page 7: ...e communication section 17 The IED section 18 Tool concept 20 Engineering concept in IEC 61850 6 21 Section 4 Communication profile 23 Section 5 Supported services 25 Section 6 Data sets and control blocks 27 Data sets 27 Report control block URCB BRCB 28 GOOSE Control Blocks GoCB 31 Section 7 Logical node data model 35 Common data objects in each logical node 35 Logical nodes for control 37 Bay c...

Page 8: ...unctions 52 Disturbance recorder RDRE 52 Disturbance report DRPRDRE 52 Logical nodes for generic references 53 Generic process I O GGIO 53 Logic rotating switch for function selection SLGAPC 53 Selector mini switch VSGAPC 55 Generic communication function for Double Point indication DPGAPC 56 Single point generic control 8 signals SPC8GAPC 57 Event counter with limit supervision L4UFCNT 60 IEC 618...

Page 9: ...uble point value GOOSEDPRCV 84 Integer Receive INTRCV 84 GOOSE function block to receive an integer value GOOSEINTRCV 84 Measured Value Receive MVRCV 85 GOOSE function block to receive a measurand value GOOSEMVRCV 85 Single Point Receive SP SPRCV 85 GOOSE function block to receive a single point value GOOSESPRCV 85 Section 9 Flexible product naming 87 Introduction 87 Mapping example 87 Mapping pos...

Page 10: ...4 ...

Page 11: ... v11 This manual is intended for the communication system engineer or system integrator responsible for pre engineering and engineering the communication setup in a substation from an IED perspective The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol 1MRK 511 440 UEN A...

Page 12: ...rt IEDs to the project structure The manual also recommends a sequence for the engineering of protection and control functions as well as communication engineering for IEC 61850 The installation manual contains instructions on how to install the IED The manual provides procedures for mechanical and electrical installation The chapters are organized in the chronological order in which the IED shoul...

Page 13: ...and technical data sorted per function The manual can be used as a technical reference during the engineering phase installation and commissioning phase and during normal service The communication protocol manual describes the communication protocols supported by the IED The manual concentrates on the vendor specific implementations The cyber security deployment guideline describes the process for...

Page 14: ... injury The caution icon indicates important information or warning related to the concept discussed in the text It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property The information icon alerts the reader of important facts and conditions The tip icon indicates advice on for example how to design your project or how to use a cer...

Page 15: ...n frames with a shaded area on their right hand side represent setting parameter signals that are only settable via the PST ECT Illustrations are used as an example and might show other products than the one the manual describes The example that is illustrated is still valid 1 5 IEC 61850 edition 1 edition 2 mapping GUID C5133366 7260 4C47 A975 7DBAB3A33A96 v5 Function block names are used in ACT ...

Page 16: ...LGAPC SLGGIO SLGAPC SMPPTRC SMPPTRC SMPPTRC SP16GAPC SP16GGIO SP16GAPC SPC8GAPC SPC8GGIO SPC8GAPC SPGAPC SPGGIO SPGAPC SSCBR SSCBR SSCBR SSIMG SSIMG SSIMG SSIML SSIML SSIML SXCBR SXCBR SXCBR SXSWI SXSWI SXSWI TEIGAPC TEIGGIO TEIGAPC TMAGAPC TMAGGIO TMAGAPC VSGAPC VSGGIO VSGAPC WRNCALH WRNCALH WRNCALH Section 1 1MRK 511 440 UEN A Introduction 10 Switchgear control unit SAM600 IO Version 2 2 IEC Com...

Page 17: ...semantic which is mandatory This manual describes how the IEC 61850 standard is applied in the IEDs References and brief descriptions of the standard are also included It is assumed that the reader has basic knowledge of the IEC 61850 standard The following parts of the IEC 61850 standard are of importance as they relate to this manual Station Configuration description Language SCL is described in...

Page 18: ...data objects For example a transformer differential or line differential protection because the standard defines only a differential protection Therefore it is possible to adapt the logical node which is defined in the standard as a logical node class The standard defines methods to describe the actually used logical node as a logical node type which is then based upon the logical node class This ...

Page 19: ...for substations and feeder equipment Common data classes IEC 61850 7 4 First edition 2003 05 Ref number IEC 61850 7 4 2003 E Communication networks and systems in substations Part 7 4 Basic communication structure for substations and feeder equipment Compatible logical node classes and data classes IEC 61850 8 1 First edition 2004 05 Ref number IEC 61850 8 1 2004 E Communication networks and syste...

Page 20: ...14 ...

Page 21: ...ums The system structure is defined by the organization of the plant structure in PCM600 The signal engineering and the signal routing are IET600 tasks signal engineering regarding DS rcb gcb GOOSE subscribers can be done also in PCM600 The IED needs to be configured with PCM600 before the system is configured with IET600 The SCL engineering must be done in an SCL engineering tool The data sets an...

Page 22: ...t sections given when an IED is integrated in the substation structure and or in the communication structure All needed logical nodes of an IED are linked to the substation section by the SCL tool A reference to GOOSE Control Blocks GoCB is included in the communication section when GoCB is configured 3 1 The substation section SEMOD129763 4 v4 The substation description in IEC 61850 6 clause 9 de...

Page 23: ...ifferent subnetworks Access points per IED to subnetworks Address IP address of LAN network is exceptionally part of the address elements Link to GoCB message in transmission direction extended during signal engineering and routing en06000101 vsd IED server Access Point AP Address GSE GoCBs Communication AP IED server Access Point AP Address GSE GoCBs Communication IED server Access Point AP Addre...

Page 24: ...nctionality is represented by logical nodes of group Information I These are the logical nodes LN ITCI IHMI and ITMI Client IEDs are the receiver of information in monitoring direction and sender of commands control These logical nodes have no data objects They are only used to link the report control blocks BRCBs from the server IEDs They have to read their information about the signals and the s...

Page 25: ... sets the various control blocks inputs from GOOSE messages In the IED series the data sets and the control blocks shall be located to LD0 The LN LPHD is a special logical node per LD and contains data objects that describe the status of the physical device the IED Each logical node represents a function and contains a number of data objects DO Each DO includes a number of data attributes DA The d...

Page 26: ... as a result of the IED configuration In PCM600 the configuration properties for SCL are handled automatically as a result of the configuration except for the GOOSE data sets IEC 61850 engineering with PCM600 PCM600 IEC 61850 Configuration tool and or IET600 PCM600 When an IED is instantiated its place in the plant structure creates the corresponding structure in the substation section in SCL The ...

Page 27: ...oss reference the signals in SMT If input signals are not defined for clients in IET600 they will not be visible in SMT Inputs GOOSE clients can also be defined in PCM600 PCM600 Import the SCD file to PCM600 to receive GOOSE data For each IED that shall receive GOOSE information the received data is connected to the applications using SMT in PCM600 To be able to import scd file to PCM600 61850 eng...

Page 28: ...at the IED tool provides the CID or ICD file for each IED These ICD CID files are then imported into the system tool and merged into a SCD file representing the complete substation or a part of the substation like one for each voltage level Section 3 1MRK 511 440 UEN A Substation Configuration description Language SCL 22 Switchgear control unit SAM600 IO Version 2 2 IEC Communication protocol manu...

Page 29: ...ommunication network has to take these two specifications and adapt their respective product to the requirements and definitions given in the standard To make this profile visible to all other partners so they can check what they can expect and what they have to support the PICS document is defined The PICS contains in a table based form the possibility of a product or product family IED server 61...

Page 30: ...09000153 V1 EN US Figure 7 Overview of functionality and profiles according to IEC 61850 8 1 Out of this content the implementation supports GOOSE TimeSync using SNTP The peer to peer vertical communication using MMS protocol suite with the T profile TCP IP For each of the above the resulting underlying protocols as stated in Figure 7 See the PICS and PIXIT for more information Section 4 1MRK 511 ...

Page 31: ...re is only one setting group control block which is located in LD0 LLN0 Logical Device0 Logical Node 0 Note that the actual number of used setting groups is defined by the parameter MaxNoSetGRP in the function SETGRPS which is configured in PST in PCM600 But six setting groups is the maximum and it cannot be exceeded Report control block For properties about report control blocks see PIXIT UnBuffe...

Page 32: ...ion block in ACT and then use the measured value given by the MVGAPC MVGAPC IEC 61850 generic communication I O functions have the event handled measured values can be added directly to the data set Generic function blocks are provided to make available to the 61850 bus signals that are not defined inside any of the available function blocks Example of such functions include SPGAPC IEC 61850 gener...

Page 33: ...e default data sets can be modified or removed in the engineering tools No RCBs are created automatically by PCM600 However the configured IEDs are delivered with RCBs for all default data sets or when templates are used LD0 SXCBR1 Pos FC ST LD0 SXSWI1 Pos FC ST LD0 SXSWI2 Pos FC ST LD0 SXSWI3 Pos FC ST LD0 SXSWI4 Pos FC ST LD0 LLN0 AppPos DATA SET LD0 LPHD SXCBR1 SCSWI1 SXSWI1 SCSWI2 SXSWI2 SCSWI...

Page 34: ...le the unbuffered is sent upon data change and not stored during interruption The content of a BRCB is listed in IEC 61850 7 2 in clause 14 The BRCB contains many attributes which are of interest to handle and secure the communication between the client and the server and may be set once as default in a project Others are of application interest in the way events are handled in a project Buffer ti...

Page 35: ...s IEC 61850 has defined in total five different TrgOp Three of them belonging to data attributes and marked per data attribute in the column TrgOp of the CDC tables in part 7 3 The other two belonging to the configuration of control blocks dchg data change Whenever a process value has changed its value either binary or a measurement a transmission is done qchg quality change Looking to the possibi...

Page 36: ...port Control description of the IED section The description of the BRCB with selected DataSet configured parameters and selected IEDs is included in the SCL file in the IED section in the LN0 structure for the LD where this LN0 belongs to en06000107 vsd LD0 SXCBR1 Pos FC ST LD0 SXSWI1 Pos FC ST LD0 SXSWI2 Pos FC ST LD0 SXSWI3 Pos FC ST LD0 SXSWI4 Pos FC ST LD0 LLN0 AppPos DATA SET IED HSI Client 1...

Page 37: ...etween IEDs on bay level in horizontal direction through the use of multicast services GOOSE messages enable fast transmission from a publisher to one or several subscribers receivers The GOOSE service model of IEC 61850 7 2 provides the possibility for fast and reliable system wide distribution of input and output data values This implementation uses a specific scheme of re transmission to achiev...

Page 38: ...it for the next re transmission If a new message is not received within that time interval the receiver assumes that the association is lost The specific intervals used by any GOOSE publisher are a local issue The timeAllowedtoLive parameter informs subscribers of how long to wait The detection time of lost GOOSE is 2 timeAllowedToLive in the subscriber This allows one lost GOOSE message and to co...

Page 39: ... with their actual value and the message is sent The subscribers who knows the address of this GOOSE message receives the telegram The GOOSE message includes a sequence number to verify that all messages are received 1MRK 511 440 UEN A Section 6 Data sets and control blocks Switchgear control unit SAM600 IO Version 2 2 IEC 33 Communication protocol manual ...

Page 40: ...34 ...

Page 41: ...ere are LN types based upon LN classes The LN type attributes are called Data Objects or DATA and are in of DO types base upon respective CDC class This allows all partners in the IEC 61850 project who need this LN to understand the LN in all details for the communication part The IEC 61850 standard does not describe the functionality and way of operation Each supplier has to describe this separat...

Page 42: ...or is influenced also by other sources independent from the Mod for example Insertion of the test handle IED configuration tool PCM600 or LHMI In case the setting operation of a function is set to Off from the LHMI or PCM600 the Beh will be set to Off independent of the value of the Mod The state Off can be set from the LHMI or the PCM600 for the functions having the setting operation Health Healt...

Page 43: ...850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 LocSwPos v1_dINS stVal ST Mon Position of the Local Remote switch q ST ...

Page 44: ...ockUpdate Oper origin orCat CO Cmd Special block command value used for blockUpdate Oper origin orIdent CO Cmd Special block command value used for blockUpdate Oper ctlNum CO Cmd Special block command value used for blockUpdate Oper T CO Cmd Special block command value used for blockUpdate Oper Test CO Cmd Special block command value used for blockUpdate Oper Check CO Cmd Special block command val...

Page 45: ...r IEC61850 Cancel origin orCat CO Cmd Command parameter for IEC61850 Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 SBOw ctlVal CO Cmd Command parameter for IEC61850 SBOw origin orCat CO Cmd Command parameter for IEC61850 SBOw origin orIdent CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Can...

Page 46: ...er origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ...

Page 47: ...locked t ST CMD_BLK Mon Timestamp Commands are blocked 7 3 Logical nodes for conversion functions 7 3 1 Integer to Boolean converter FCVB 7 3 1 1 Integer to Boolean 16 conversion with logic node representation ITBGAPC SEMOD158419 1 v3 PID 3627 LOGICALNODEDATA v3 LN type LN prefix LN class Function block name IB16FCVB revision 0 IB16 FCVB ITBGAPC Table 4 ITBGAPC Logical node data DO name DO type DA...

Page 48: ...ameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 stVal ST Mon Integer to be converted to bit pattern OUT1 to OUT16 q ST Mon Quality Integer to be converted to bit pattern OUT1 to OUT16 t ST Mon Timestamp Integer to be converted to bit pattern OUT1 to OUT16 ctlModel CF Used by CH 7 3 2 B...

Page 49: ... Behaviour parameter OutInt b_dINS stVal ST OUT Mon Output value q ST OUT Mon Quality Output value t ST OUT Mon Timestamp Output value 7 4 Logical nodes for protection functions 7 4 1 Protection trip conditioning PTRC 7 4 1 1 Logic for group alarm ALMCALH PID 6510 LOGICALNODEDATA v1 LN type LN prefix LN class Function block name ALMCALH revision 1 ALM CALH ALMCALH Table 6 ALMCALH Logical node data...

Page 50: ... prefix LN class Function block name INDCALH revision 1 IND CALH INDCALH Table 7 INDCALH Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode ...

Page 51: ...rt signal from phase L2 dirPhsB ST Mon Direction signal from phase L2 phsC ST STL3 Mon Start signal from phase L3 dirPhsC ST Mon Direction signal from phase L3 q ST START Mon Quality Common start signal t ST START Mon Timestamp Common start signal Op a_dACT general ST TRIP Mon General trip output signal phsA ST TRL1 Mon Trip signal from phase L1 phsB ST TRL2 Mon Trip signal from phase L2 phsC ST T...

Page 52: ...EC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 SPTr v1_dSPS stVal ST TR1P Mon Tripping single pole q ST TR1P Mon Quality Tripping single pole t ST TR1P Mon Timestamp Tripping single pole TwoPTr v1_dSPS stVal ST TR2P Mon Tripping two pole q ST TR2P Mon Quality Tripping two pole t ST TR2P Mon Timestamp Tripping two pole TPTr v1_dSPS stVal ST ...

Page 53: ...ter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter GrAlm a_dSPS stVal ST WARNING Mon OR function betweeen inputs 1 to 16 q ST WARNING Mon Quality OR function betweeen inputs 1 to 16 t ST WARNING Mon Timestamp OR function betweeen inputs 1 to 16 7 5 Syste...

Page 54: ...tag Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 OpCntRs f_dINC Oper ctlVal CO Cmd Mapping tag Oper origin orCat CO Cmd Mapping tag Oper origin orIdent CO Cmd Mapping tag Oper ctlNum CO Cmd Mapping tag Oper T CO Cmd Mapping tag Oper Test CO Cmd Mapping tag Oper Check CO ...

Page 55: ...OGICALNODEDATA v3 LN type LN prefix LN class Function block name LPHD revision 6 LPHD LPHD Table 12 LPHD Logical node data DO name DO type DA name FC T Signal Mon C md Description PhyNam b_dDPL swRev DC Firmware version serNum DC Serial Number model DC IEDModel for IEC61850 PhyHealth n_dINS stVal ST PhyHealth Mon Physical health q ST PhyHealth Mon Quality Physical health t ST PhyHealth Mon Timesta...

Page 56: ...imestamp Behaviour parameter for 61850 NamPlt ln0_dLPL swRev DC Firmware version Health n_dINS stVal ST Mon Physical health q ST Mon Quality Physical health t ST Mon Timestamp Physical health 7 5 4 Access point diagnostic for redundant Ethernet ports RCHLCCH PID 6819 LOGICALNODEDATA v2 LN type LN prefix LN class Function block name RCHLCCH revision 1 RCH LCCH RCHLCCH Table 14 RCHLCCH Logical node ...

Page 57: ... ErrorRateA Mon Channel A redundancy error rate q ST ErrorRateA Mon Quality Channel A redundancy error rate t ST ErrorRateA Mon Timestamp Channel A redundancy error rate RedFerCh b_dINS stVal ST ErrorRateB Mon Channel B redundancy error rate q ST ErrorRateB Mon Quality Channel B redundancy error rate t ST ErrorRateB Mon Timestamp Channel B redundancy error rate 7 5 5 Access point diagnostic for no...

Page 58: ...p Access point link status 7 6 Logical nodes for protection related functions 7 6 1 Disturbance recorder RDRE 7 6 1 1 Disturbance report DRPRDRE GUID 0B12001D 5AD2 451B 8AFE 0920B947F5C1 v1 PID 3949 LOGICALNODEDATA v3 LN type LN prefix LN class Function block name DRPRDRE revision 0 DRP RDRE DRPRDRE Table 16 DRPRDRE Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_d...

Page 59: ...nce fault number t ST FaultNumber Mon Timestamp Disturbance fault number 7 7 Logical nodes for generic references 7 7 1 Generic process I O GGIO 7 7 1 1 Logic rotating switch for function selection SLGAPC SEMOD114936 1 v5 PID 6641 LOGICALNODEDATA v2 LN type LN prefix LN class Function block name SLGGIO revision 7 SL GGIO SLGAPC Table 17 SLGAPC Logical node data DO name DO type DA name FC T Signal ...

Page 60: ...EC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 q ST Mon Quality Position t ST Mon Timestamp Position ctlModel CF Control model type for jump cmd sboTimeout CF Maximum time between select and execute signals for jump cmd sboClass CF Select for many...

Page 61: ...ameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Ti...

Page 62: ...or IEC61850 Cancel Test CO Cmd Command parameter for IEC61850 SBOw Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 SBOw Check CO Cmd Command parameter for IEC61850 stVal ST POSITION Mon Position indication integer q ST POSITION Mon Quality Position indication integer t ST POSITION Mon Timestamp Position indication integer stSeld ST Mon Select conditions ...

Page 63: ...uality Double point indication t ST POSITION Mon Timestamp Double point indication 7 7 1 4 Single point generic control 8 signals SPC8GAPC SEMOD176448 1 v3 PID 3575 LOGICALNODEDATA v3 LN type LN prefix LN class Function block name SPC8GGIO revision 2 SPC8 GGIO SPC8GAPC Table 20 SPC8GAPC Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mod...

Page 64: ...er Check CO Cmd Command parameter for IEC61850 SPCSO2 d_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parame...

Page 65: ...61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 SPCSO6 d_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO C...

Page 66: ...parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 7 7 1 5 Event counter with limit supervision L4UFCNT GUID C7139F45 E03E 440A 85FD 2102B6470688 v1 PID 3553 LOGICALNODEDATA v3 LN type LN prefix LN class Function block name L4UFCNT revision 0 L4U FCNT L4UFCNT Table 21 L4UFCNT Logical node data DO name DO type DA name FC T Signal Mon C md Description CntRs a_dBCR actVal ST VALU...

Page 67: ...T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 Lim1 v1_dSPS stVal ST LIMIT1 Mon Counted value is larger than or equal to CounterLimit1 q ST LIMIT1 Mon Quality Counted value is larger than or equal to CounterLimit1 t ST LIMIT1 Mon Timestamp Counted value is larger than or equal to CounterLimit1 Lim2 v1_dSPS st...

Page 68: ...FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter ...

Page 69: ...1850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Ind c_dSPS stVal ST OUT1 Mon Output 1 status q ST OUT1 Mon Quality Output 1 status t ST OUT1 Mon Timestamp Output 1 status Ind2 c_dSPS stVal ST OUT2 Mon Output 2 status q ST OUT2 Mon Quality Output 2 status t ST OUT2 Mon Timestamp Ou...

Page 70: ...tus Ind12 c_dSPS stVal ST OUT12 Mon Output 12 status q ST OUT12 Mon Quality Output 12 status t ST OUT12 Mon Timestamp Output 12 status Ind13 c_dSPS stVal ST OUT13 Mon Output 13 status q ST OUT13 Mon Quality Output 13 status t ST OUT13 Mon Timestamp Output 13 status Ind14 c_dSPS stVal ST OUT14 Mon Output 14 status q ST OUT14 Mon Quality Output 14 status t ST OUT14 Mon Timestamp Output 14 status Ind...

Page 71: ...Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 AnIn a_dMV rangeC hhLim f CF MV hhLim High High limit multiplied with the base prefix multiplication factor rangeC hLim f CF MV hLim High limit multiplied with the base prefix multiplication factor rangeC lLim f CF MV lLim Low limit multiplied with the base prefix multiplication factor rangeC llLim f CF ...

Page 72: ... Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter Out...

Page 73: ...O Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp ...

Page 74: ...reached the warning limit q ST WARNING Mon Quality Indicator of the integrated time has reached the warning limit t ST WARNING Mon Timestamp Indicator of the integrated time has reached the warning limit AccTms v2_dMV mag f MX ACCTIME Mon Integrated elapsed time in seconds q MX ACCTIME Mon Quality Integrated elapsed time in seconds t MX ACCTIME Mon Timestamp Integrated elapsed time in seconds 7 8 ...

Page 75: ...Mon The number of days CB has been inactive q ST INADAYS Mon Quality The number of days CB has been inactive t ST INADAYS Mon Timestamp The number of days CB has been inactive RmnLif v1_dINS stVal ST CBLIFEPH Mon CB Remaining life of respective phase q ST CBLIFEPH Mon Quality CB Remaining life of respective phase t ST CBLIFEPH Mon Timestamp CB Remaining life of respective phase RsAccAPwr v1_dSPC O...

Page 76: ...er for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 RsSprChaTm v1_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Chec...

Page 77: ...p Accum I CurrExponent integr over CB open travel time exceeds alarm limit APwrLO v1_dSPS stVal ST IPOWLOPH Mon Accum I CurrExponent integr over CB open travel time exceeds lockout limit q ST IPOWLOPH Mon Quality Accum I CurrExponent integr over CB open travel time exceeds lockout limit t ST IPOWLOPH Mon Timestamp Accum I CurrExponent integr over CB open travel time exceeds lockout limit LonTmAlm ...

Page 78: ...vel ColOpn v1_dSPS stVal ST TRCMD Mon Open command issued to CB q ST TRCMD Mon Quality Open command issued to CB t ST TRCMD Mon Timestamp Open command issued to CB TmmsCls v2_dMV mag f MX TTRVCL Mon Travel time of the CB during closing operation q MX TTRVCL Mon Quality Travel time of the CB during closing operation t MX TTRVCL Mon Timestamp Travel time of the CB during closing operation TmmsOpn v2...

Page 79: ...32C501A v1 Since there is no current measurement functionality in SAM600 IO evaluation of the following parameters are not possible in the circuit breaker condition monitoring function SSCBR Circuit breaker status Remaining life of the circuit breaker Contact erosion estimation Circuit breaker contact travel time Setting parameters AccmPwrAlm AccmPwrLo CBLifeAlm RmnNumOp ClsAlm OpnAlm AccmAPwr RsA...

Page 80: ...ES_LO Mon Quality Pressure below lockout level t ST PRES_LO Mon Timestamp Pressure below lockout level PresAlm a_dSPS stVal ST PRES_ALM Mon Pressure below alarm level q ST PRES_ALM Mon Quality Pressure below alarm level t ST PRES_ALM Mon Timestamp Pressure below alarm level TmpAlm a_dSPS stVal ST TEMP_ALM Mon Temperature above alarm level q ST TEMP_ALM Mon Quality Temperature above alarm level t S...

Page 81: ...GICALNODEDATA v3 LN type LN prefix LN class Function block name SSIML revision 0 S SIML SSIML Table 29 SSIML Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850...

Page 82: ...ality Level service value t MX LEVEL Mon Timestamp Level service value Tmp b_dMV mag f MX TEMP Mon Temperature of the insulation medium q MX TEMP Mon Quality Temperature of the insulation medium t MX TEMP Mon Timestamp Temperature of the insulation medium LORs v1_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cm...

Page 83: ...Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 BlkCls a_dSPC Oper ctlVal CO Cmd Special block command value Oper origin orCat CO Cmd Special block command value Oper origin orIdent CO Cmd Sp...

Page 84: ...process level q ST Mon Quality Indication that the function is in local mode process level t ST Mon Timestamp Indication that the function is in local mode process level OpCnt b_dINS stVal ST CNT_VAL Mon Operation counter value q ST CNT_VAL Mon Quality Operation counter value t ST CNT_VAL Mon Timestamp Operation counter value Pos c_dDPC stVal ST POSITION Mon Apparatus position indication q ST POSI...

Page 85: ...pe LN prefix LN class Function block name SXSWI revision 1 S XSWI SXSWI Table 31 SXSWI Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mod...

Page 86: ...lock command value Oper ctlNum CO Cmd Special block command value Oper T CO Cmd Special block command value Oper Test CO Cmd Special block command value Oper Check CO Cmd Special block command value stVal ST OP_BLKD Mon Indication that the function is blocked for open commands q ST OP_BLKD Mon Quality Indication that the function is blocked for open commands t ST OP_BLKD Mon Timestamp Indication t...

Page 87: ...reak 2 Disconnector 3 EarthSw 4 HighSpeedEarthSw t ST Mon Timestamp 1 LoadBreak 2 Disconnector 3 EarthSw 4 HighSpeedEarthSw BlkUpd v1_dSPC Oper ctlVal CO Cmd Special block command value Oper origin orCat CO Cmd Special block command value Oper origin orIdent CO Cmd Special block command value Oper ctlNum CO Cmd Special block command value Oper T CO Cmd Special block command value Oper Test CO Cmd ...

Page 88: ...82 ...

Page 89: ...inOut2 a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping q ST Mon Quality Internal parameter tag to handle 61850 mapping TagBinOut3 a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping TagBinOut4 a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping TagBinOut5 a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping TagBinOut6 a_dSPS stVal ST M...

Page 90: ...ock to receive a double point value GOOSEDPRCV GUID 279C13CC 7C70 4217 8AC3 7D6682B7D355 v1 PID 3981 LOGICALNODEDATA v2 LN type LN prefix LN class Function block name DPGREC instance 1 revision 0 DP GREC GOOSEDPRCV Table 33 GOOSEDPRCV Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description TagDPOut a_dDPS stVal ST Mon Internal parameter tag to handle 61850 mapping q S...

Page 91: ...md Description TagMVOut a_dMV mag f MX Mon Internal parameter tag to handle 61850 mapping q MX Mon Quality Internal parameter tag to handle 61850 mapping 8 5 Single Point Receive SP SPRCV 8 5 1 GOOSE function block to receive a single point value GOOSESPRCV GUID 15FDB5EB 8BF3 4548 8410 A4139F6D92EF v1 PID 2527 LOGICALNODEDATA v17 LN type LN prefix LN class Function block name BINSGREC instance 1 r...

Page 92: ...86 ...

Page 93: ... Customer specific naming convention for communication can be used Other IEDs and station level equipment can be defined from the customer specific communication model Error tracing of communication can be the same between different installations 9 1 1 Mapping example GUID DD7F097C 1D72 4BA2 8684 61B54EF0D00C v1 FunctionA Non affected function views IED 61850 model Customer 61850 model FPN mapping...

Page 94: ...everal levels in the structure Logical Node level LN to LN Data Object level DO to DO Data Attribute level DA to DA Custom logical device name LDName can be used for addressing When the mapping is performed there are some requirements that must be fulfilled between the IED model and the customer model One attribute in the customer model can only be mapped to one attribute in the IED model However ...

Page 95: ...model the DOs in the customer model might be inconsistent with respect to quality in the case of different operational states of the IED Functions When several LNs in the customer model are mapped to one function in the IED the Mod of the function will affect all the customer LNs Several other use cases like this exist By understanding the concept of mapping from IED functions and IED model to cus...

Page 96: ...90 ...

Page 97: ...vice data unit AWG American Wire Gauge standard BBP Busbar protection BFOC 2 5 Bayonet fibre optic connector BFP Breaker failure protection BI Binary input BIM Binary input module BOM Binary output module BOS Binary outputs status BR External bistable relay BS British Standards BSR Binary signal transfer function receiver blocks BST Binary signal transfer function transmit blocks C37 94 IEEE ANSI ...

Page 98: ...r Transient Data Exchange format for Disturbance recorder according to IEEE ANSI C37 111 1999 IEC 60255 24 Contra directional Way of transmitting G 703 over a balanced line Involves four twisted pairs two of which are used for transmitting data in both directions and two for transmitting clock signals COT Cause of transmission CPU Central processing unit CR Carrier receive CRC Cyclic redundancy ch...

Page 99: ...nterference EnFP End fault protection EPA Enhanced performance architecture ESD Electrostatic discharge F SMA Type of optical fibre connector FAN Fault number FCB Flow control bit Frame count bit FOX 20 Modular 20 channel telecommunication system for speech data and protection signals FOX 512 515 Access multiplexer FOX 6Plus Compact time division multiplexer for the transmission of up to seven dup...

Page 100: ...mittee IEC 60044 6 IEC Standard Instrument transformers Part 6 Requirements for protective current transformers for transient performance IEC 60870 5 103 Communication standard for protection equipment A serial master slave protocol for point to point communication IEC 61850 Substation automation communication standard IEC 61850 8 1 Communication protocol standard IEEE Institute of Electrical and ...

Page 101: ...d on Ethernet networks IP is a connectionless best effort packet switching protocol It provides packet routing fragmentation and reassembly through the data link layer 2 Ingression protection according to IEC 60529 IP 20 Ingression protection according to IEC 60529 level 20 IP 40 Ingression protection according to IEC 60529 level 40 IP 54 Ingression protection according to IEC 60529 level 54 IRF I...

Page 102: ...es the fault but perhaps it should not have seen it PCI Peripheral component interconnect a local data bus PCM Pulse code modulation PCM600 Protection and control IED manager PC MIP Mezzanine card standard PELV circuit Protected Extra Low Voltage circuit type according to IEC60255 27 PMC PCI Mezzanine card POR Permissive overreach POTT Permissive overreach transfer trip Process bus Bus or LAN used...

Page 103: ... factor pluggable abbreviation Optical Ethernet port explanation SLM Serial communication module SMA connector Subminiature version A A threaded connector with constant impedance SMT Signal matrix tool within PCM600 SMS Station monitoring system SNTP Simple network time protocol is used to synchronize computer clocks on local area networks This reduces the requirement to have accurate hardware clo...

Page 104: ...rrent transformer class according to IEC TRM Transformer Module This module transforms currents and voltages taken from the process into levels suitable for further signal processing TYP Type identification UMT User management tool Underreach A term used to describe how the relay behaves during a fault condition For example a distance relay is underreaching when the impedance presented to it is gr...

Page 105: ...etic alphabet stands for Z which stands for longitude zero UV Undervoltage WEI Weak end infeed logic VT Voltage transformer X 21 A digital signalling interface primarily used for telecom equipment 3IO Three times zero sequence current Often referred to as the residual or the earth fault current 3UO Three times the zero sequence voltage Often referred to as the residual voltage or the neutral point...

Page 106: ...100 ...

Page 107: ...101 ...

Page 108: ... AB Grid Automation Products 721 59 Västerås Sweden Phone 46 0 21 32 50 00 abb com protection control Copyright 2017 ABB All rights reserved Specifications subject to change without notice 1MRK 511 440 UEN ...

Reviews: