Table 276: CMSUM Output signals
Name
Type
Description
I3P
SIGNAL
Summed three-phase currents
IRES
SIGNAL
Calculated residual current of summed three-
phase currents
3.20.20
Transformer data combiner OLGAPC
3.20.20.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transformer data combiner
OLGAPC
OLGAPC
OLGAPC
3.20.20.2
Function block
Figure 160: Function block
3.20.20.3
Functionality
The transformer data combiner function OLGAPC is intended for the voltage
regulator function OL5ATCC.
3.20.20.4
Operation principle
The function of OLGAPC is to collect data from a parallel transformer via GOOSE
communication. The
TR_DAT
output, which contains the combined input data, is
connected to the OL5ATCC function block.
3.20.20.5
Application
See the application example in
.
1MRS759142 F
Basic functions
REX640
Technical Manual
285