Table 239: MVI4GAPC Output signals
Name
Type
Description
OUT1
INT32
Integer output value 1
OUT2
INT32
Integer output value 2
OUT3
INT32
Integer output value 3
OUT4
INT32
Integer output value 4
3.20.10
Analog value event creation with scaling SCA4GAPC (ANSI
SCA4)
3.20.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Analog value event creation with
scaling
SCA4GAPC
SCA4
SCA4
3.20.10.2
Function block
Figure 142: Function block
3.20.10.3
Functionality
The analog value event creation with scaling function SCA4GAPC is used for scaling
the analog value. It allows creating events from analog values.
The analog value received via the
AIn_VALUE
input is scaled with the
Scale ratio n
setting. The scaled value is available on the
AOn_VALUE
output.
Analog input range is from –10000.0 to 10000.0.
Analog output range is from –2000000.0 to 2000000.0.
If the value of the
AIn_VALUE
input exceeds the analog input range,
AOn_VALUE
is set to 0.0.
Basic functions
1MRS759142 F
254
REX640