Figure 685: Fault distance estimate triggering moment definitions
Fault loops “AB Fault”, “BC Fault” or “CA Fault”
Fault loops “AB Fault”, “BC Fault” or “CA Fault” are used for phase-to-phase short
circuit faults as well as in the case of a two-phase-to-earth fault if the individual
earth faults are located at the same feeder.
shows the phase-to-phase
fault loop model. The following impedances are measured and stored in the
recorded data of SCEFRFLO.
Flt point resistance
R
fault
=
2
(Equation 299)