
Figure 658: Inrush current in transformer
It is recommended to use the second harmonic and the waveform based
inrush blocking from the transformer differential protection function
TR2PTDF, if available.
5.1.7
Signals
5.1.7.1
INRPHAR Input signals
Table 1104: INRPHAR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
BLOCK
BOOLEAN
0=False
Block input status
5.1.7.2
INRPHAR Output signals
Table 1105: INRPHAR Output signals
Name
Type
Description
BLK2H
BOOLEAN
Second harmonic based
block
Protection related functions
1MRS759142 F
1160
REX640
Technical Manual