4.10.7.2
STTPMSU Output signals
Table 1037: STTPMSU Output signals
Name
Type
Description
OPR_IIT
BOOLEAN
Operate/trip signal for ther-
mal stress.
OPR_STALL
BOOLEAN
Operate/trip signal for stall-
ing protection.
MOT_START
BOOLEAN
Signal to show that motor
startup is in progress
LOCK_START
BOOLEAN
Lock out condition for restart
of motor.
4.10.8
STTPMSU Settings
Table 1038: STTPMSU Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Motor start-up A
1.0...10.0
xIn
0.1
2.0
Motor starting cur-
rent
Motor start-up
time
1...80
s
1
5
Motor starting time
Lock rotor time
2...120
s
1
10
Permitted stalling
time
Str over delay time 0...60000
ms
1
100
Time delay to check
for completion of
motor startup peri-
od
Table 1039: STTPMSU Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Start detection A
0.1...10.0
xIn
0.1
1.5
Current value for
detecting starting
of motor.
Table 1040: STTPMSU Non group settings (Basic)
Parameter
Values
(Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation
Off / On
Operation
mode
1=IIt
2=IIt, CB
3=IIt + stall
4=IIt + stall,
CB
1=IIt
Motor start-
up operation
mode
Table continues on the next page