Action
Description
Close
Clicking Close closes this instance of the Fault Record tool. All open instances are
closed when PCM600 is closed.
File
File menu for Save and Exit actions
Edit
Copy All in the Edit menu allows to copy all the fault records which can then be
pasted to a word processor and saved on the local machine without having to save
the records as a .txt file.
Additionally the user can select any particular fault record and right-click to copy the
selected record.
5.6
IED Compare
IED Compare is used to compare the IED configurations of two IEDs of the same type.
It generates a text report which lists the differences between the IED configurations.
IED Compare provides an option to compare an IED configuration stored in
PCM600, IED or .pcmi file. IED Compare can compare certain types of IED
configurations and parameters.
•
Application configuration
•
Display configuration
•
GOOSE receive configuration
•
Parameters
Application comparison also compares the system function blocks.
Display comparison compares the LHMI page configurations.
Detailed instructions are shown in PCM600 documentation.
5.6.1
Starting IED Compare
•
Start
IED Compare
in the shortcut menu in plant structure.
1.
In the PCM600 plant structure, right-click
Substation
,
Voltage level
,
Bay
or
IED
.
2.
Select
IED Compare
.
•
Start
IED Compare
from the PCM600 main menu.
Section 5
1MRS759117 A
Protection and control engineering
90
REX640
Engineering Manual