In the following example, it is assumed that PCM600 and IET600 are used as the
system configuration tools. Another option is to use IEC 61850 Configuration tool or
Application Configuration in PCM600. In that case, the SCL file export and import
(steps 1 and 3) are not needed. For more information on the GOOSE engineering in
IEC 61850 Configuration tool and Application Configuration, see the IEC 61850
engineering guide.
1. SCL files are exported from PCM600. In this case, a SCD file. It is also possible
to export other SCL file types.
2. Horizontal and vertical communication is configured using the station
configuration tool, for example, IEC 61850 Configuration tool or IET600.
3. SCL files are imported to a PCM600 project. In this case, it is the updated SCD
file.
SCD file
do IED engineering
export SCD file
PCM600 (1)
create project
import SCD file
configure data sets
configure Report CBs
configure GOOSE CBs
export SCD file
IET 600
(2)
import SCD file
link GOOSE input data
Write to IED
PCM600 (3)
SCD file
IED 1
IED n
IED 2
IED n -1
GUID-6FBAA0CB-90AE-4668-ABAF-B772F9CC350B V1 EN
Figure 111:
IEC 61850: signal engineering procedure flow when a complete
station is exported as a SCD file
7.3.1
Exporting SCL files from PCM600
A pre-condition for exporting SCL files from PCM600 is that all IEDs in the project
must be engineered in PCM600. The IEDs require a unique name and IP addresses and
they must be set according to the project definitions. IED configurations must be
finalized as far as possible before starting the IEC 61850 configuration part.
7.3.1.1
Exporting SCD files
1.
Select the station in the
Plant Structure
view.
1MRS759117 A
Section 7
IEC 61850 communication engineering
REX640
135
Engineering Manual