Table 14:
LON node information parameters
Parameter
Range
Default
Unit
Parameter description
NeuronID*
0 - 12
Not loaded
-
Neuron hardware identification number in
hexadecimal code
Location
0 - 6
No value
-
Location of the node
*Can be viewed on the local HMI
ADE settings are available on the local HMI under
Main menu/Configuration/
Communication/Station communicaton/LON/ADE:1
Table 15:
ADE Non group settings (basic)
Name
Values (Range) Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation
TimerClass
Slow
Normal
Fast
-
-
Slow
Timer class
LON commands are available on the local HMI under
Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON pot/
Service Pin Messae/Generate service pin message
Table 16:
LON commands
Command
Command description
ServPinMess
Command with confirmation. Transfers the node address to the LON Network Tool.
7.2
Optical budget calculation for serial communication with
LON
Table 17:
Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation
-11 dB
- 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um
4 dB
-
0.3 dB/m plastic: 620 nm - 1mm
-
3 dB
Margins for installation, aging, and so on
5 dB
2 dB
Losses in connection box, two contacts (0.75 dB/contact)
1.5 dB
-
Table continues on next page
Section 7
1MRK 504 165-UUS -
Establishing connection and verifying the LON communication
68
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...