The setting parameter
WEI
is set to
Echo & Trip
.
1.
Apply input signals according Table
.
2.
Activate the receive (CR) signal.
3.
After the IED has operated, turn off the input signals.
4.
Check that trip, send signal, and indication are obtained.
The ECHO output gives only a 200 ms pulse.
11.11.3.3
Completing the test
Continue to test another function or end the test by changing the
TESTMODE
setting to
Disabled
. Restore connections and settings to their original values, if they were changed
for testing purposes.
11.11.4
Scheme communication logic for residual overcurrent
protection ECPSCH (85)
Prepare the IED for verification of settings outlined in Section
.
Before testing the communication logic for residual overcurrent protection function
ECPSCH (85), the four step residual overcurrent protection function EF4PTOC (51N/
67N) has to be tested according to the corresponding instruction. Once this is done,
continue with the instructions below.
If the current reversal and weak-end infeed logic for ground-fault protection is included,
proceed with the testing according to the corresponding instruction after testing the
communication logic for residual overcurrent protection. The current reversal and weak-
end-infeed functions shall be tested together with the permissive scheme.
11.11.4.1
Testing the directional comparison logic function
Blocking scheme
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
265
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...