18.5.3
Setting guidelines
IP14841-1 v1
M12811-3 v3
The input parameters for the Event function (EVENT) can be set individually via the
local HMI (
Main Menu/Settings / IED Settings / Monitoring / Event Function
) or
via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
M12811-5 v3
The inputs can be set individually as:
•
NoEvents
•
OnSet
, at pick-up of the signal
•
OnReset
, at drop-out of the signal
•
OnChange
, at both pick-up and drop-out of the signal
•
AutoDetect
, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an optimized
way to minimize the load on the station bus.
18.6
Disturbance report DRPRDRE
IP14584-1 v2
1MRK 504 163-UUS A
Section 18
Monitoring
Transformer protection RET670 2.2 ANSI
885
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...