16.1.3.2
Delta blocking scheme
GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1
Set
Operation
=
Enabled
Set
SchemeType
=
DeltaBlocking
Set
tCoord
= 0 s
Set
tSendMin
= 0 s
Set
Unblock
=
Disabled
(Set to
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaV
= 5 %VB
Set
Delta3I0
= 10 %IB
Set
Delta3V0
= 5 %VB
16.1.3.3
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
Enabled
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
16.1.3.4
Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
Enabled
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
16.1.3.5
Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
1MRK 504 163-UUS A
Section 16
Scheme communication
Transformer protection RET670 2.2 ANSI
819
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...