15.2.1.1
Bay control QCBAY
M16595-3 v9
The Bay control (QCBAY) is used to handle the selection of the operator place per bay.
The function gives permission to operate from two main types of locations either from
Remote (for example, control centre or station HMI) or from Local (local HMI on the
IED) or from all (Local and Remote). The Local/Remote switch position can also be
set to Off, which means no operator place selected that is, operation is not possible
either from local or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set to discriminate
between commands with orCat station and remote (2 and 3). The selection is then done
through the IEC 61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay. There are two different blocking alternatives:
•
Blocking of update of positions
•
Blocking of commands
IEC13000016-2-en.vsd
IEC13000016 V2 EN-US
Figure 316:
APC - Local remote function block
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
703
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...