The threshold voltages
VDeadBusEnerg
and
VDeadLineEnerg
, have to be set to a
value greater than the value where the network is considered not to be energized. A
typical value can be 40% of the base voltages.
A disconnected line can have a considerable potential due to, for
instance, induction from a line running in parallel, or by being fed via
the extinguishing capacitors in the circuit breakers. This voltage can be
as high as 30% or more of the base line voltage.
Because the setting ranges of the threshold voltages
VLiveBusEnerg
/
VLiveLineEnerg
and
VDeadBusEnerg
/
VDeadLineEnerg
partly overlap each other, the setting conditions
may be such that the setting of the non-energized threshold value is higher than that of
the energized threshold value. The parameters must therefore be set carefully to avoid
overlapping.
VMaxEnerg
This setting is used to block the closing when the voltage on the live side is above the
set value of
VMaxEnerg
.
tAutoEnerg
and
tManEnerg
The purpose of the timer delay settings,
tAutoEnerg
and
tManEnerg
, is to ensure that
the dead side remains de-energized and that the condition is not due to a temporary
interference. Should the conditions not persist for the specified time, the delay timer is
reset and the procedure is restarted when the conditions are fulfilled again. Circuit
breaker closing is thus not permitted until the energizing condition has remained
constant throughout the set delay setting time.
15.2
Apparatus control APC
IP14560-1 v2
15.2.1
Application
IP14931-1 v1
M13443-4 v13
The apparatus control is a functionality for control and supervising of circuit breakers,
disconnectors, and grounding switches within a bay. Permission to operate is given
after evaluation of conditions from other functions such as interlocking, synchronism
check, operator place selection and external or internal blockings.
The complete apparatus control function is not included in this product,
and the information below is included for understanding of the
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
697
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...