The relative angle of the generator is shown a contingency in the power system,
causing un-damped oscillations. After a few periods of the oscillation the swing
amplitude gets to large and the stability cannot be maintained.
If the excitation of the generator gets too low there is a risk that the generator cannot
maintain synchronous operation. The generator will slip out of phase and operate as an
induction machine. Normally the under-excitation protection will detect this state and
trip the generator before the pole slip. For this fault the under-excitation protection and
PSPPPAM (78) function will give mutual redundancy.
The operation of a generator having pole slip will give risk of damages to the generator
block.
•
At each pole slip there will be significant torque impact on the generator-turbine
shaft.
•
In asynchronous operation there will be induction of currents in parts of the
generator normally not carrying current, thus resulting in increased heating. The
consequence can be damages on insulation and stator/rotor iron.
•
At asynchronous operation the generator will absorb a significant amount of
reactive power, thus risking overload of the windings.
PSPPPAM (78) function shall detect out of step conditions and trip the generator as
fast as possible if the locus of the pole slip is inside the generator. If the centre of pole
slip is outside the generator, situated out in the power grid, the first action should be to
split the network into two parts, after line protection action. If this fails there should be
operation of the generator pole slip protection, to prevent further damages to the
generator block.
8.16.3
Setting guidelines
SEMOD167596-1 v1
SEMOD167582-4 v4
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
Operation
: With the parameter
Operation
the function can be set
Enabled
or
DIsabled
.
MeasureMode
: The voltage and current used for the impedance measurement is set by
the parameter
MeasureMode
. The setting possibilities are:
PosSeq
,
AB
,
BC
, or
CA
. If
all phase voltages and phase currents are fed to the IED the
PosSeq
alternative is
recommended (default).
Further settings can be illustrated in figure
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
469
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...