The above parameters are defined for OLTC1. Similar parameters shall be set for
second on-load tap-changer designated with OLTC2 in the parameter names, for three–
winding differential protection.
7.1.3.8
Differential current alarm
M15266-337 v6
Differential protection continuously monitors the level of the fundamental frequency
differential currents and gives an alarm if the pre-set value is simultaneously exceeded
in all three phases. This feature can be used to monitor the integrity of on-load tap-
changer compensation within the differential function. The threshold for the alarm
pickup level is defined by setting parameter
IDiffAlarm
. This threshold should be
typically set in such way to obtain operation when on-load tap-changer measured value
within differential function differs for more than two steps from the actual on-load tap-
changer position. To obtain such operation set parameter
IDiffAlarm
equal to two times
the on-load tap-changer step size (For example, typical setting value is 5% to 10% of
base current). Set the time delay defined by parameter
tAlarmDelay
two times longer
than the on-load tap-changer mechanical operating time (For example, typical setting
value 10s).
7.1.3.9
Open CT detection
M15266-340 v5
The Transformer differential function has a built-in, advanced open CT detection
feature. This feature can block the unexpected operation created by the Transformer
differential function in case of open CT secondary circuit under normal load condition.
An alarm signal can also be issued to station operational personnel to make remedy
action once the open CT condition is detected.
The following setting parameters are related to this feature:
•
Setting parameter
OpenCTEnable
enables/disables this feature
•
Setting parameter
tOCTAlarmDelay
defines the time delay after which the alarm
signal will be given
•
Setting parameter
tOCTReset
defines the time delay after which the open CT
condition will reset once the defective CT circuits have been rectified
•
Once the open CT condition has been detected, then all the differential protection
functions are blocked except the unrestraint (instantaneous) differential protection
The outputs of open CT condition related parameters are listed below:
•
OpenCT
: Open CT detected
•
OpenCTAlarm
: Alarm issued after the setting delay
•
OpenCTIN
: Open CT in CT group inputs (1 for input 1 and 2 for input 2)
•
OpenCTPH
: Open CT with phase information (1 for phase A, 2 for phase B, 3 for
phase C)
Section 7
1MRK 504 163-UUS A
Differential protection
144
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...