Name
Values (Range)
Unit
Step
Default
Description
IMaxCh6
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 6
ValueMinCh6
-10000000000.000
-
10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh6
ValueMaxCh6
-10000000000.000
-
10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh6
23.2.11.5
Monitored data
PID-4110-MONITOREDDATA v5
Table 663:
MIM Monitored data
Name
Type
Values (Range)
Unit
Description
STATUS
BOOLEAN
0=Ok
1=Error
-
Milliampere input module
status
CH1
REAL
-
-
Analog input 1
CH2
REAL
-
-
Analog input 2
CH3
REAL
-
-
Analog input 3
CH4
REAL
-
-
Analog input 4
CH5
REAL
-
-
Analog input 5
CH6
REAL
-
-
Analog input 6
CH1
REAL
-
A
Service value analog input 1
CH2
REAL
-
A
Service value analog input 2
CH3
REAL
-
A
Service value analog input 3
CH4
REAL
-
A
Service value analog input 4
CH5
REAL
-
A
Service value analog input 5
CH6
REAL
-
A
Service value analog input 6
23.2.11.6
Technical data
SEMOD55438-1 v1
M6389-1 v5
Table 664:
MIM - mA input module
Quantity:
Rated value:
Nominal range:
Input resistance
R
in
= 194 Ohm
-
Input range
±5, ±10, ±20 mA
0-5, 0-10, 0-20, 4-20 mA
-
Power consumption
each mA board
each mA input
£
2 W
£
0.1 W
-
Section 23
1MRK 511 408-UUS A
IED hardware
844
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...