![ABB Relion RES670 Technical Manual Download Page 825](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485825.webp)
Maximum 176 binary input channels may be activated simultaneously
with influencing factors within nominal range.
23.2.8
Binary output modules (BOM)
IP14536-1 v1
23.2.8.1
Introduction
M6938-3 v4
The binary output module has 24 independent output relays and is used for trip output
or any signaling purpose.
23.2.8.2
Design
M1819-3 v4
The binary output module (BOM) has 24 software supervised output relays. Each pair
of relays have a common power source input to the contacts, see figure
should be considered when connecting the wiring to the connection terminal on the
back of the IED.
The high closing and carrying current capability allows connection directly to breaker
trip and closing coils. If breaking capability is required to manage fail of the breaker
auxiliary contacts normally breaking the trip coil current, a parallel reinforcement is
required.
For configuration of the output signals, refer to section
1MRK 511 408-UUS A
Section 23
IED hardware
Phasor measurement unit RES670 2.2 ANSI