PID-6428-SETTINGS v3
Table 619:
3PHSUM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
SummationType
Group2
Group1-Group2
Group2-Group1
-(Group2)
-
-
Group2
Summation type
DFTReference
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
External DFT ref
-
-
InternalDFTRef
DFT reference for external output
Table 620:
3PHSUM Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
FreqMeasMinVal
5 - 200
%
1
10
Amplitude limit for frequency calculation in %
of UBase
22.10.5
Operation principle
SEMOD55749-4 v5
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
22.11
Global base values GBASVAL
GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1
22.11.1
Identification
GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Global base values
GBASVAL
-
-
Section 22
1MRK 511 408-UUS A
Basic IED functions
794
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...