19.4.9.6
Operation principle
GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v5
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
Freeze
0
1
0
Incoming data with q=Invalid
Freeze
0
1
0
Incoming data with q=test
Freeze
0
1
1
Incoming data with q=test+oldData
Freeze
0
1
1
Receiver in block
Freeze
0
1
0
Receiver in block and communication
error
Freeze
0
0
0
Receiver in test mode and incoming data
with q= Normal
Updated
1
1
0
Receiver in test mode and incoming data
with q= Test
Updated
1
1
1
Communication Error
Freeze
0
0
0
The input of this GOOSE block must be linked either in SMT by means
of a cross or in ACT by means of a GOOSE connection (in case easy
GOOSE engineering is enabled) to receive the measured value.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
Section 19
1MRK 511 408-UUS A
Station communication
640
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...