PID-6828-OUTPUTSIGNALS v3
Table 480:
GOOSEDPRCV Output signals
Name
Type
Description
DPOUT
INTEGER
Double point output
DATAVALID
BOOLEAN
Data valid for double point output
COMMVALID
BOOLEAN
Communication valid for double point output
TEST
BOOLEAN
Test output
19.4.7.5
Settings
PID-6828-SETTINGS v3
Table 481:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
19.4.7.6
Operation principle
GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
0
0
1
0
Incoming data with q=Invalid
0
0
1
0
Incoming data with q=test
0
0
1
1
Incoming data with q=test+oldData
0
0
1
1
Receiver in block
0
0
1
0
Receiver in block and communication
error
0
0
0
0
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
0
0
0
0
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
635
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...