Name
Values (Range)
Unit
Step
Default
Description
MV lLim
-5000.00 - 5000.00
xBase
0.01
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
MV llLim
-5000.00 - 5000.00
xBase
0.01
-900.00
Low Low limit multiplied with the base prefix
(multiplication factor)
MV min
-5000.00 - 5000.00
xBase
0.01
-1000.00
Minimum value multiplied with the base prefix
(multiplication factor)
MV max
-5000.00 - 5000.00
xBase
0.01
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Deadband
Reporting type
MV limHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for
all limits)
19.4.6.5
Monitored data
PID-6753-MONITOREDDATA v1
Table 478:
MVGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
REAL
-
-
Magnitude of deadband value
RANGE
INTEGER
1=High
2=Low
3=High-High
4=Low-Low
0=Normal
-
Range
19.4.6.6
Operation principle
SEMOD55936-5 v7
Upon receiving an analog signal at its input, Generic communication function for
Measured Value (MVGAPC) will give the instantaneous value of the signal and the
range, as output values. Additional configuration is needed with PCM600 or IET600 to
get the IEC 61850-8-1 communication established. For more information see the
Engineering manual.
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
633
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...