OUTOR
GROUP
SIGNAL
-
-
Output status logic OR gate
for input 1 to 16
19.4.5.6
Operation principle
SEMOD55725-5 v7
Upon receiving a signal at its input, Generic communication function for Single Point
indication (SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment
or system that requests this signal. Additional configuration is needed with PCM600 or
IET600 to get the IEC 61850-8-1 communication established For more information
refer to the Engineering manual.
19.4.6
Generic communication function for Measured Value
MVGAPC
SEMOD55402-1 v3
19.4.6.1
Functionality
SEMOD55872-5 v10
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
631
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...