![ABB Relion RES670 Technical Manual Download Page 221](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485221.webp)
8.3.4
Signals
PID-4151-INPUTSIGNALS v4
Table 106:
NS4PTOC (46I2) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group connection for operate current
I3PDIR
GROUP
SIGNAL
-
Group connection for directional current
V3P
GROUP
SIGNAL
-
Group connection for polarizing voltage
BLOCK
BOOLEAN
0
General block
BLKTR
BOOLEAN
0
Block of trip
BLK1
BOOLEAN
0
Block of step 1 (Pickup and trip)
BLK2
BOOLEAN
0
Block of step 2 (Pickup and trip)
BLK3
BOOLEAN
0
Block of step 3 (Pickup and trip)
BLK4
BOOLEAN
0
Block of step 4 (Pickup and trip)
MULTPU1
BOOLEAN
0
When activated, the pickup multiplier is in use for
step1
MULTPU2
BOOLEAN
0
When activated, the pickup multiplier is in use for
step2
MULTPU3
BOOLEAN
0
When activated, the pickup multiplier is in use for
step3
MULTPU4
BOOLEAN
0
When activated, the pickup multiplier is in use for
step4
PID-4151-OUTPUTSIGNALS v4
Table 107:
NS4PTOC (46I2) Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TRST1
BOOLEAN
Trip signal from step 1
TRST2
BOOLEAN
Trip signal from step 2
TRST3
BOOLEAN
Trip signal from step 3
TRST4
BOOLEAN
Trip signal from step 4
PICKUP
BOOLEAN
Common pickup signal
PU_ST1
BOOLEAN
Pickup signal step 1
PU_ST2
BOOLEAN
Pickup signal step 2
PU_ST3
BOOLEAN
Pickup signal step 3
PU_ST4
BOOLEAN
Pickup signal step 4
PUFW
BOOLEAN
Forward directional pickup signal
PUREV
BOOLEAN
Reverse directional pickup signal
1MRK 511 408-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.2 ANSI
215
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...