In order to enable current polarizing, the magnitude of the polarizing current shall be
bigger than a minimum level defined by setting parameter
IPolMin
.
Dual polarizing
When dual polarizing is selected, the function will use the vectorial sum of the voltage
based and current based polarizing in accordance with the following formula:
(
)
0
0
0
3
3
s
VTotPol VVPol VIPol
V
Z
IPol
V
RNPol
jXNPol
IPol
=
+
= -
+
×
= -
+
+
×
ANSIEQUATION1878 V1 EN-US
(Equation 20)
Vpol and Ipol can be either zero sequence component or negative sequence component
depending upon the user selection.
Then the phasor of the total polarizing voltage VTotPol will be used, together with the
phasor of the operating current, to determine the direction of the ground fault (forward/
reverse).
8.2.7.3
External polarizing for ground-fault function
M13941-144 v6
The individual steps within the protection can be set as non-directional. When this
setting is selected, it is possible via the function binary input BLKx to provide external
directional control (that is, torque control) by, for example, using one of the following
functions if available in the IED:
1. Distance protection directional function.
2. Negative sequence polarized general current and voltage multi purpose protection
function.
8.2.7.4
Directional detection for ground fault function
GUID-FC382DD3-E2C8-455E-8CD5-1DE1793DD178 v6
Zero sequence components will be used for detecting directionality for the ground fault
function. In some cases, zero sequence quantities might detect directionality
incorrectly. In such a scenario, negative sequence quantities will be used. The user can
select either zero sequence components or negative sequence components for detecting
directionality with the parameter
SeqTypeIPol
. I3PDIR input is always connected to the
same source as I3P input.
8.2.7.5
Base quantities within the protection
M13941-152 v6
The base quantities are entered as global settings for all functions in the IED. Base
current (
IBase
) shall be entered as rated phase current of the protected object in
primary amperes. Base voltage (
VBase
) shall be entered as rated phase-to-phase
voltage of the protected object in primary kV.
Section 8
1MRK 511 408-UUS A
Current protection
202
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...