![ABB Relion RES670 Technical Manual Download Page 193](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485193.webp)
restraint feature is active, the OC4PTOC 51_67 function output signal ST2NDHRM
will be set to the logical value
one
.
a
b
a>b
BLOCK
AND
I
OP
Extract second
harmonic current
component
Extract
fundamental
current component
X
2ndHarmStab
a
b
a>b
a
b
a>b
0.07*IBase
IEC13000014-2-en.vsd
2ndH_BLOCK_Int
IEC13000014 V2 EN-US
Figure 56:
Second harmonic blocking
8.1.8
Technical data
M12342-1 v20
Table 98:
OC4PTOC (51/67) technical data
Function
Setting range
Accuracy
Trip current, step 1-4
(5-2500)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Reset ratio
> 95% at (50–2500)% of
lBase -
Minimum operate current, step 1-4
(1-10000)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Relay characteristic angle (RCA)
(40.0–65.0) degrees
±
2.0 degrees
Relay operating angle (ROA)
(40.0–89.0) degrees
±
2.0 degrees
Second harmonic blocking
(5–100)% of fundamental
±
2.0% of I
n
Independent time delay at 0 to 2 x I
set
, step
1-4
(0.000-60.000) s
±
0.2% or
±
35 ms
whichever is greater
Minimum trip time for inverse curves , step
1-4
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
Inverse time characteristics, see table
,
16 curve types
See table
,
and table
Trip time, pickup non-directional at 0 to 2 x
I
set
Min. = 15 ms
-
Max. = 30 ms
Reset time, pickup non-directional at 2 x I
set
to 0
Min. = 15 ms
-
Max. = 30 ms
Table continues on next page
1MRK 511 408-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.2 ANSI
187
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...