Section 6
Wide area measurement system
6.1
Protocol reporting via IEEE 1344 and C37.118
PMUREPORT
GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v1
6.1.1
Identification
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Protocol reporting via IEEE 1344 and
C37.118
PMUREPORT
-
-
6.1.2
Application
GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4
The phasor measurement reporting block moves the phasor calculations into an
IEEE C37.118 and/or IEEE 1344 synchrophasor frame format. The PMUREPORT
block contains parameters for PMU performance class and reporting rate, the
IDCODE and Global PMU ID, format of the data streamed through the protocol,
the type of reported synchrophasors, as well as settings for reporting analog and
digital signals.
The message generated by the PMUREPORT function block is set in accordance
with the IEEE C37.118 and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero
sequence in case of 3-phase phasor and L1, L2 or L3 in case of single phase
phasor), PMU's Service class (Protection or Measurement), Phasor representation
(polar or rectangular) and the data types for phasor data, analog data and frequency
data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP
group clients for multicast or unicast transmission of phasor data from the IED.
More information regarding synchrophasor communication structure and
TCP/UDP configuration is available in section
C37.118 Phasor Measurement Data
Streaming Protocol Configuration
.
Multiple PMU functionality can be configured in the IED, which can stream out
same or different data at different reporting rates or different performance (service)
classes. There are 2 instances of PMU functionality available in the IED. Each
instance of PMU functionality includes a set of PMU reporting function blocks
tagged by the same instance number (1 or 2). As shown in the following figures,
each set of PMU reporting function blocks includes PMUREPORT,
1MRK 511 407-UEN C
Section 6
Wide area measurement system
Phasor measurement unit RES670 2.2 IEC
87
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...