Figure 151:
Initial condition for weak-end infeed
13.4.3
Setting guidelines
IP15042-1 v1
M13933-4 v5
The parameters for the current reversal and weak-end infeed logic for residual
overcurrent protection function are set via the local HMI or PCM600.
Common base IED values for primary current (
IBase
), primary voltage (UBase)
and primary power (
SBase
) are set in a Global base values for settings function
GBASVAL.
GlobalBaseSel
: It is used to select a GBASVAL function for reference of base
values.
13.4.3.1
Current reversal
M13933-6 v5
The current reversal function is set on or off by setting the parameter
CurrRev
to
On
or
Off
. Time delays shall be set for the timers
tPickUpRev
and
tDelayRev
.
tPickUpRev
is chosen shorter (<80%) than the breaker opening time, but minimum
20 ms.
tDelayRev
is chosen at a minimum to the sum of protection reset time and the
communication reset time. A minimum
tDelayRev
setting of 40 ms is
recommended.
The reset time of the directional residual overcurrent protection (EF4PTOC) is
typically 25 ms. If other type of residual overcurrent protection is used in the
remote line end, its reset time should be used.
The signal propagation time is in the range 3 – 10 ms/km for most types of
communication media. In communication networks small additional time delays
are added in multiplexers and repeaters. Theses delays are less than 1 ms per
process. It is often stated that the total propagation time is less than 5 ms.
When a signal picks-up or drops out there is a decision time to be added. This
decision time is highly dependent on the interface between communication and
protection used. In many cases an external interface (teleprotection equipment) is
used. This equipment makes a decision and gives a binary signal to the protection
device. In case of analog teleprotection equipment typical decision time is in the
range 10 – 30 ms. For digital teleprotection equipment this time is in the range 2 –
10 ms.
Section 13
1MRK 506 375-UEN A
Scheme communication
356
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...