tMFPosDiff
: Time delay for activation of the output OUTOFPOS.
12.5.2.3
TCMYLTC and TCLYLTC general settings
SEMOD171501-150 v6
LowVoltTap
: This gives the tap position for the lowest LV-voltage.
HighVoltTap
: This gives the tap position for the highest LV-voltage.
mALow
: The mA value that corresponds to the lowest tap position. Applicable
when reading of the tap position is made via a mA signal.
mAHigh
: The mA value that corresponds to the highest tap position. Applicable
when reading of the tap position is made via a mA signal.
CodeType
: This setting gives the method of tap position reading.
UseParity
: Sets the parity check
On
/
Off
for tap position reading when this is made
by Binary, BCD, or Gray code.
tStable
: This is the time that needs to elapse after a new tap position has been
reported to TCMYLTC until it is accepted.
CLFactor
: This is the factor designated “a” in
operates at nominal load current (current measured on the HV-side), the
ContactLife counter decrements with 1, irrespective of the setting of
CLFactor
.
The setting of this factor gives the weighting of the deviation with respect to the
load current.
InitCLCounter
: The ContactLife counter monitors the remaining number of
operations (decremental counter). The setting
InitCLCounter
then gives the start
value for the counter that is, the total number of operations at rated load that the tap
changer is designed for.
EnabTapCmd
: This setting enables/disables the lower and raise commands to the
tap changer. It shall be
On
for voltage control, and
Off
for tap position feedback to
the transformer differential protection T2WPDIF or T3WPDIF.
TCMYLTC and TCLYLTC Setting group
SEMOD171501-157 v3
General
Operation
: Switching the TCMYLTC or TCLYLTC function
On
/
Off
.
IBase
: Base current in primary Ampere for the HV-side of the transformer.
tTCTimeout
: This setting gives the maximum time interval for a raise or lower
command to be completed.
tPulseDur
: Length of the command pulse (URAISE/ULOWER) to the tap changer.
It shall be noticed that this pulse has a fixed extension of 4 seconds that adds to the
setting value of
tPulseDur
.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
331
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...