9.3.3.1
High impedance earthed systems
M13853-18 v10
In high impedance earthed systems, an earth fault on one phase will cause a voltage
collapse in that phase. However, the other healthy phase voltage will raise to full
phase-to-phase voltage value. The residual voltage sum 2U
0
will raise to the same
phase-to-phase value during earth fault.
9.3.3.2
Solidly earthed systems
GUID-EA622F55-7978-4D1C-9AF7-2BAB5628070A v8
In solidly earthed systems, an earth fault on one phase is indicated by voltage
collapse in that phase. The other healthy phase will still have normal phase-to-earth
voltage. The residual sum 2U
0
will have the same value as the remaining phase-to-
earth voltage.
9.3.3.3
Settings for two step residual overvoltage protection
M13853-21 v13
Parameters for ROV2PTOV application function are set via the local HMI or
Protection and Control Manager PCM600.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base
values.
Operation
: This is used for residual overvoltage protection
Off
/
On
.
UBase
(given in
GlobalBaseSel
) is used as voltage reference for the set pickup
values.
UBase
shall be set equal to rated phase-to-phase voltage. Note that the set
value for
UBase
will be multiplied by factor 0.5 within the ROV2PTOV function.
The voltage can be fed to the IED in different ways:
1. The IED is fed from two VTs connected phase-to-ground, where the residual
voltage 2U
0
is calculated internally within the protection.
2. The IED is fed from a single voltage transformer connected to the neutral point
of a power transformer in the power system. In this connection the protection
is fed by the voltage UN=U
0
(single input). Section
Analog inputs
in the
Application manual explains how the analog input needs to be set.
The setting parameters described below are identical for the two steps (
n
= step 1
and 2). Therefore the setting parameters are described only once.
OperationStepn
: This is to enable/disable operation of step n.
Un>
: Set operate overvoltage operation value for step
n
, given as % of residual
voltage corresponding to
UBase
:
(%)
(
) / 2
Un
UBase kV
IECEQUATION050 V2 EN-US
(Equation 66)
Section 9
1MRK 506 375-UEN A
Voltage protection
202
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...