2.3.66
LD0.CMMXU1 Phase current limit supervision (1)
Table 69:
LD0.CMMXU1 Phase current limit supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
2752
172.00
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2753
172.01
.mcd
2754
172.02
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2755
172.03
.mcd
2756
172.04
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
2757
172.05
.mcd
2758
172.06
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
2759
172.07
.mcd
2.3.67
LD0.RESCMMXU1 Residual current limit supervision (1)
Table 70:
LD0.RESCMMXU1 Residual current limit supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
2760
172.08
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2761
172.09
.mcd
2762
172.10
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2763
172.11
.mcd
2.3.68
LD0.VMMXU1 Phase voltage limit supervision (1)
Table 71:
LD0.VMMXU1 Phase voltage limit supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMMXU1
2784
174.00
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2785
174.01
.mcd
2786
174.02
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2787
174.03
.mcd
2788
174.04
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
2789
174.05
.mcd
2790
174.06
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
2791
174.07
.mcd
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
41
Point List Manual