2.3.37
LD0.T1PTTR1 Thermal overload protection (1)
Table 40:
LD0.T1PTTR1 Thermal overload protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.T1PTTR1
2972
185.12
.Str.general
START
General start
1=Start
2973
185.13
.mcd
2974
185.14
.AlmThm.general
ALARM
Thermal alarm
1=Alarm
2975
185.15
.mcd
2976
186.00
.Op.general
OPERATE
General operate
1=Operate
2977
186.01
.mcd
2.3.38
CTRL.CCBRBRF1 Circuit breaker (1) failure protection
Table 41:
CTRL.CCBRBRF1 Circuit breaker (1) failure protection
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CCBRBRF1
2826
176.10
.InStr.stVal
START
CBFP start command
1=Start
2827
170.11
.mcd
2828
176.12
.Str.general
CB_FAULT_AL
Timer running
1=Running
2829
176.13
.mcd
2830
176.14
.OpEx.general
TRBU
Fail, external trip
1=Ext.trip
2831
176.15
.mcd
2832
177.00
.OpIn.general
TRRET
Internal re-trip
1=Re-trip
2833
177.01
.mcd
2.3.39
LD0.INRPHAR1 Three-phase inrush detection (1)
Table 42:
LD0.INRPHAR1 Three-phase inrush detection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.INRPHAR1
2964
185.04
.Str.general
BLK2H
General start
1=Start
2965
185.05
.mcd
2966
185.06
.Str.phsA
phsA start
1=Start
2967
185.07
.mcd
2968
185.08
.Str.phsB
phsB start
1=Start
2969
185.09
.mcd
2970
185.10
.Str.phsC
phsC start
1=Start
2971
185.11
.mcd
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
31
Point List Manual