BitA
RegA
IEC 61850 name
SA name
Description
Values
3111
194.07
.mcd
3112
194.08
.Str.phsB
phsB start
1=Start
3113
194.09
.mcd
3114
194.10
.Str.phsC
phsC start
1=Start
3115
194.11
.mcd
3116
194.12
.Op.general
OPERATE
General operate
1=Operate
3117
194.13
.mcd
2.3.33
LD0.PSPTUV1 Positive-sequence undervoltage protection
(1)
Table 36:
LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PSPTUV1
3118
194.14
.Str.general
START
General start
1=Start
3119
194.15
.mcd
3120
195.00
.Str.phsA
phsA start
1=Start
3121
195.01
.mcd
3122
195.02
.Str.phsB
phsB start
1=Start
3123
195.03
.mcd
3124
195.04
.Str.phsC
phsC start
1=Start
3125
195.05
.mcd
3126
195.06
.Op.general
OPERATE
General operate
1=Operate
3127
195.07
.mcd
2.3.34
LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)
Table 37:
LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.NSPTOV1
3128
195.08
.Str.general
START
General start
1=Start
3129
195.09
.mcd
3130
195.10
.Str.phsA
phsA start
1=Start
3131
195.11
.mcd
3132
195.12
.Str.phsB
phsB start
1=Start
3133
195.13
.mcd
3134
195.14
.Str.phsC
phsC start
1=Start
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
29
Point List Manual