2.3.30
LD0.PHPTOV1 Phase overvoltage protection (1)
Table 33:
LD0.PHPTOV1 Phase overvoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV1
3088
193.00
.Str.general
START
General start
1=Start
3089
193.01
.mcd
3090
193.02
.Str.phsA
phsA start
1=Start
3091
193.03
.mcd
3092
193.04
.Str.phsB
phsB start
1=Start
3093
193.05
.mcd
3094
193.06
.Str.phsC
phsC start
1=Start
3095
193.07
.mcd
3096
193.08
.Op.general
OPERATE
General operate
1=Operate
3097
193.09
.mcd
2.3.31
LD0.PHPTOV2 Phase overvoltage protection (2)
Table 34:
LD0.PHPTOV2 Phase overvoltage protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV2
3098
193.10
.Str.general
START
General start
1=Start
3099
193.11
.mcd
3100
193.12
.Str.phsA
phsA start
1=Start
3101
193.13
.mcd
3102
193.14
.Str.phsB
phsB start
1=Start
3103
193.15
.mcd
3104
194.00
.Str.phsC
phsC start
1=Start
3105
194.01
.mcd
3106
194.02
.Op.general
OPERATE
General operate
1=Operate
3107
194.03
.mcd
2.3.32
LD0.PHPTOV3 Phase overvoltage protection (3)
Table 35:
LD0.PHPTOV3 Phase overvoltage protection (3)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV3
3108
194.04
.Str.general
START
General start
1=Start
3109
194.05
.mcd
3110
194.06
.Str.phsA
phsA start
1=Start
Table continues on next page
Section 2
1MRS757822 B
Modbus data mappings
28
Recloser Protection and Control RER615
Point List Manual