3
3
1
REQ650 (A01)
Z
SC
: Low
Three phase short circuit
Line protection zone 1 reach
IEC10000150-1-en.vsd
IEC10000150 V1 EN
Figure 16:
Fault for step 2 setting
Recommended current setting is therefore 2000 A.
1.
Set
DirMode2
to
Reverse
.
2.
Set
Characterist1
is set to
IEC Def. Time
.
For the time delay characteristic, definite time is used in this network.
3.
Set
I2>
to
200%
of
IBase
(2000 A primary current).
4.
Set
t2
to
0.4 s
.
3.1.5.4
Calculating settings for step 3
The phase overcurrent protection shall never trip for load current in extreme high load
situations. The maximum load current through the coupler bay is 750 A (the same as
the CT-rated current), corresponding to about 190 MVA. The resetting ratio is 0.95.
The minimum setting can be calculated:
1
3
750 790
0.95
I
A
> ³ ×
×
=
EQUATION2344 V1 EN
1.
Set
DirMode3
to
Non-directional
.
2.
Set
Characterist1
is set to
IEC Def. Time
.
1MRK 505 291-UEN A
Section 3
REQ650 setting examples
51
Application manual