group, and the bus voltage is above 80% of the bus base voltage
UBase
, according
to the setting
GblBaseSelBus
.
•
DBLL
, Dead Bus Live Line, the bus voltage is below 40% of the bus base voltage
UBase
, according to the setting
GblBaseSelBus
about the Global Base Value
group, and the line voltage is above 80% of the line base voltage
UBase
,
according to the setting
GblBaseSelLine
.
•
Both
, energizing can be done in both directions,
DLLB
or
DBLL
.
ManEnergDBDL
If the parameter is set to
On
, manual closing is enabled when line voltage is below 40%
of the line base voltage
UBase
, according to the setting
GblBaseSelLine
about the
Global Base Value group, and when bus voltage is below 40% of the bus base voltage
UBase, according to the setting
GblBaseSelBus
and also
ManEnerg
is set to
DLLB
,
DBLL
or
Both
.
tAutoEnerg
and
tManEnerg
The purpose of the timer delay settings,
tAutoEnerg
and
tManEnerg
, is to ensure that
the dead side remains de-energized and that the condition is not due to a temporary
interference. Should the conditions not persist for the specified time, the delay timer
is reset and the procedure is restarted when the conditions are fulfilled again. Circuit
breaker closing is thus not permitted until the energizing condition has remained
constant throughout the set delay setting time.
10.2
Autorecloser for 3-phase operation SMBRREC
10.2.1
Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autorecloser for 3-phase operation
SMBRREC
O->I
SYMBOL-L V1 EN
79
10.2.2
Application
Automatic reclosing is a well-established method for the restoration of service in a
power system after a transient line fault. The majority of line faults are flashover arcs,
which are transient by nature. When the power line is switched off by the operation of
line protection and line breakers, the arc de-ionizes and recovers its ability to
withstand voltage at a somewhat variable rate. Thus, a certain dead time with a de-
energized line is necessary. Line service can then be resumed by automatic reclosing
1MRK 505 291-UEN A
Section 10
Control
197
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...