6.14.3
Directional underpower protection GUPPDUP
6.14.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional underpower protection
GUPPDUP
P <
2
SYMBOL-LL V2 EN
37
6.14.3.2
Setting guidelines
GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
UBase
) and (
SBase
).
Operation
: With the parameter
Operation
the function can be set
On
/
Off
.
Mode
: The voltage and current used for the power measurement. The setting
possibilities are shown in table
.
For reverse power applications
PosSeq
or
Arone
modes are strongly recommended.
Table 21:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
L1, L2, L3
*
*
*
1
1
2
2
3
3
L
L
L
L
L
L
S
U
I
U
I
U
I
=
×
+
×
+
×
EQUATION1697 V1 EN
(Equation 56)
Arone
*
*
1 2
1
2 3
3
L L
L
L L
L
S
U
I
U
I
=
×
-
×
EQUATION1698 V1 EN
(Equation 57)
PosSeq
*
3
PosSeq
PosSeq
S
U
I
= ×
×
EQUATION1699 V1 EN
(Equation 58)
L1L2
*
*
1 2
1
2
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1700 V1 EN
(Equation 59)
L2L3
*
*
2 3
2
3
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1701 V1 EN
(Equation 60)
L3L1
*
*
3 1
3
1
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1702 V1 EN
(Equation 61)
Table continues on next page
1MRK 505 291-UEN A
Section 6
Current protection
149
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...