17.1.4
Signals
Table 710:
PCFCNT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
READ_VAL
BOOLEAN
0
Initiates an additional pulse counter reading
BI_PULSE
BOOLEAN
0
Connect binary input channel for metering
RS_CNT
BOOLEAN
0
Resets pulse counter value
Table 711:
PCFCNT Output signals
Name
Type
Description
INVALID
BOOLEAN
The pulse counter value is invalid
RESTART
BOOLEAN
The reported value does not comprise a complete
integration cycle
BLOCKED
BOOLEAN
The pulse counter function is blocked
NEW_VAL
BOOLEAN
A new pulse counter value is generated
SCAL_VAL
REAL
Scaled value with time and status information
17.1.5
Settings
Table 712:
PCFCNT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
EventMask
NoEvents
ReportEvents
-
-
NoEvents
Report mask for analog events from pulse
counter
CountCriteria
Off
RisingEdge
Falling edge
OnChange
-
-
RisingEdge
Pulse counter criteria
Scale
1.000 - 90000.000
-
0.001
1.000
Scaling value for SCAL_VAL output to unit
per counted value
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
-
-
Count
Measured quantity for SCAL_VAL output
tReporting
0 - 3600
s
1
60
Cycle time for reporting of counter value
Section 17
1MRK502052-UEN B
Metering
982
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...